120
Analog Input Units
Section 5-1
6.
Click Adjustment.
The Unit Adjustment Window will be displayed.
7.
Click the Down Arrow and select the input words and the input range to be
adjusted.
8.
Apply the input voltage or input current corresponding to 0% to the input
terminal on the Analog Input Unit.
9.
Click Fix Offset Value when the appropriate input voltage or input current
has been applied according to step 8.
The offset will be set so that the input voltage or input current are converted
to a value of 0%, and the value of the offset will be stored in the EEPROM
in the Analog Input Unit. Reset the Unit to enable the new setting.
10. Apply the input voltage or input current corresponding to 100% to the input
terminal on the Analog Input Unit.
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...