Basic Procedure
Section 2-1
2-1
Basic Procedure
The basic operating procedure is shown below. For details about settings and
connections, refer to DeviceNet Operation Manual (W267). For explanations
about Slave Units, refer to SECTION 4 Basic I/O Unit Specifications and SEC-
TION 5 Special I/O Unit Specifications.
Determine the MULTIPLE
I/O TERMINAL I/O
specifications.
Inputs:
Number of points/input type/connection type
Outputs:
Number of points/input type/connection type
Analog inputs:
Number of points
Analog outputs:
Number of points
Temperature inputs:
Number of points
Pulse inputs (counter): Number of points
Select the I/O Units.
Commu-
nications
Unit (1)
Transistor Input
Terminal
block
Connec-
tor
High-den-
sity con-
nector
Unit
Relay Output
Analog
Mount and connect the
Communications Unit and
I/O Units.
Mount Units on DIN track (DIN 35-mm track: all Units).
Connect I/O Unit Connecting Cabled and end connector.
Connect Communications Unit internal power supply (24 VDC
−
15%/+10%).
Connect I/O power supply (24 VDC
−
15%/+10%) for each Transistor Input/Output Unit and Relay
Output Unit.
Connect I/O power supply (24 VDC
−
15%/+10%) for each Analog Input/Output Unit and
Temperature Input Unit, as well as power supply for each Counter Unit encoder, using a separate
power supply from the above.
Connect I/O to each I/O Unit.
Set the DIP switches for the
Communications Unit,
Analog Input Units, Analog
Output Units, and
Temperature Input Units.
Set the node number of the Communications Unit as a DeviceNet Slave, and the hold/clear output
settings for the baud rate and communications errors.
Set the Analog Input Unit, Analog Output Unit, and Temperature Input Unit ranges and other
specifications. (When setting the Analog Input Unit, Analog Output Unit, and Temperature Input
Unit ranges from the Configurator, set the DIP switch to Software Setting Enable.)
Connect to the DeviceNet
Master Unit.
Connect the Communications Unit to the DeviceNet Master Unit using the DeviceNet
Communications Cable.
Turn ON the power.
Turn ON the PC power supply.
Turn ON the DeviceNet communications power supply.
Turn ON the Communications Unit internal power supply.
Turn ON the I/O power supply to individual I/O Units.
Set the Scan List Enable
switch.
Set to enable the DeviceNet Master Unit scan list (from a PC Peripheral Device or
the Configurator).
Check the operation.
Check the I/O Unit interface status.
Check the indicators on all Units.
The following indications are normal:
Communications Unit MS indicator: Lit green
Communications Unit NS indicator: Lit green
TS indicators for I/O Units:
Lit green
Check that the data for the I/O words allocated in the I/O memory (with default allocations, in the
DeviceNet area) of the CPU Unit of the PC is being correctly read and written by the CPU Unit.
1
2
+
+
+
16 points 16 points 32 points
16 points 16 points 32 points
16 points
8 points 4 points
8 points
Analog
Input
Output
4
5
6
7
9
10
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Unit
Transistor Output
Terminal
block
Connec-
tor
High-den-
sity con-
nector
Terminal
block
Counter
1 points
Input
Unit
Check the specifications.
The combined total of input points and output points for each Communications Unit is 1,024 max.
The total current supplied from the Communications Unit to each I/O Unit (I/O Unit interface current
consumption) is 0.4 A max.
3
Set using the Configurator.
Set as required for the Communications Unit, Analog Input Units, Analog Output Units, and
Temperature Input Units using the DeviceNet Configurator (versions 1.11 and later).
8
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...