100
Analog Input Units
Section 5-1
Input Range Settings
As shown in the following table, the DIP switch input range settings are for two
inputs each.
Note If input range setting is performed using the Configurator (version 1.11 or
later), it is possible to make the setting for each point.
Internal Circuits
Terminal Arrangement
Pin 1
Pin 2
Pin 3
Input range for inputs 0 and 1
Pin 4
Pin 5
Pin 6
Input range for inputs 2 and 3
OFF
OFF
OFF
0 to 5 V
ON
OFF
OFF
1 to 5 V
OFF
ON
OFF
0 to 10 V
ON
ON
OFF
–10 to 10 V
OFF
OFF
ON
4 to 20 mA
ON
OFF
ON
0 to 20 mA
Other than the above
Cannot be set
I/O Unit
interface
Internal
power
supply
Insulating DC
to DC
converter
Input circuit
4 circuits
I/O Unit
interface
I/O Unit
interface
Photocoupler
Internal
circuits
Photocoupler
24 VDC
+
24 VDC
−
510 k
Ω
250
Ω
510 k
Ω
V+
−
I+