161
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
lected in step 7) on the Temperature Input Unit from the standard voltage/
current generator.
Wait approximately 1 minute for the input to stabilize, then click Fix upper-
limit Value.
The calibrated upper limit will be stored in the EEPROM in the Temperature
Input Unit.
10. Compensate for bias. Turn OFF the standard voltage/current generator,
and enable the cold junction compensator (close the contacts) as shown
below. Check that the cold junction compensator is functioning at 0
°
C.
With sensors R, S, and B, the margin of error at close to 0
°
C is great, so
set the input type to a K thermocouple to compensate. Wait approximately
40 minutes for the temperature to stabilize, then click Fix Bias Shift Value.
The bias compensation will be stored in the EEPROM in the Temperature
Input Unit.
11. Repeat steps 7 to 10 to adjust other inputs as necessary.
Input type
Range (
°
C)
Range (
°
F)
Input voltage
R
0 to 1700
0 to 3000
20 mV
S
0 to 1700
0 to 3000
20 mV
K
–200 to 1300
–300 to 2300
50 mV
K
0.0 to 500.0
0.0 to 900.0
20 mV
J
–100 to 850
–100 to 1500
50 mV
J
0.0 to 400.0
0.0 to 750.0
20 mV
T
–200.0 to 400.0
–300.0 to 700.0
20 mV
L
–100 to 850
–100 to 1500
50 mV
L
0.0 to 400.0
0.0 to 750.0
20 mV
B
100 to 1800
300 to 3200
20 mV
Temperature Input Unit
(GT1-TS04T)
Compensating conductor
Cold junction compensator
Contacts closed
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...