150
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
DIP Switch and Rotary
Switch Settings
The DIP switch and rotary switch are located on the left side of the cassette
on the Temperature Input Units (GT1-TS04T/TS04P). Remove the cassette
from the Unit to set the DIP switch and rotary switch.
Note Before detaching or attaching the Cassette or making DIP switch or rotary
switch settings, be sure that the power supply to the I/O Unit (including power
supply to I/O Unit interface) is OFF.
Operating Specification Settings
Note
1.
When setting the input range using a DeviceNet Configurator, use version
1.20 or later. If pin 4 is ON, and the Configurator is not used to make the
settings, all input ranges will be set to K (–200 to 1300
°
C) or Pt100 (–200
to 650
°
C).
2.
If input ranges are set using the Configurator (version 1.20 or later), it is
possible to make different settings for each point.
Input Type and Input Range Settings
The following input types and input ranges are determined by the number set
on the rotary switch. The input type and input range made using the rotary
switch are the same for all 4 input points.
GT1-TS04T
Operating specifications
Temperature units
Number of decimal places used
Software setting enable/disable
Input type
Input range
DIP switch
Function
Setting
Setting contents
1
Temperature unit
OFF
°
C (factory-set)
ON
°
F
2
Number of decimal
places used (refer to
Converted Data on
page 153)
OFF
Normal Mode (0 or 1 digit after
the decimal point, depending
on the input) (factory-set)
ON
2-decimal-place Mode
3
Reserved for system use
OFF
Must be set to OFF (factory-
set).
4
Software setting enable/
disable
OFF
Set the input range using the
rotary switch (factory-set).
ON
Set the input range using the
Configurator. (See note.)
Number
Input type
Range (
°
C)
Range (
°
F)
0
R
0 to 1700
0 to 3000
1
S
0 to 1700
0 to 3000
2 (factory-set)
K
–200 to 1300
–300 to 2300
3
K
0.0 to 500.0
0.0 to 900.0
4
J
–100 to 850
–100 to 1500
5
J
0.0 to 400.0
0.0 to 750.0
6
T
–200.0 to 400.0
–300.0 to 700.0
7
L
–100 to 850
–100 to 1500
8
L
0.0 to 400.0
0.0 to 750.0
9
B
100 to 1800
300 to 3200
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...