36
Communications Unit
Section 4-1
4-1
Communications Unit
The Communications Unit connects the MULTIPLE I/O TERMINAL to the
DeviceNet Network. Connections for a maximum of eight I/O Units can be
made with one Communications Unit.
Specifications
This product has been tested in the test laboratory of a third party authorized
by ODVA and has been approved as conforming to ODVA Conformance Soft-
ware Ver. 2.0-1.00.
Item
Specification
Model
DRT1-COM
DeviceNet com-
munications
power supply
Voltage range
11 to 25 VDC (supplied from the DeviceNet commu-
nications connector)
Unit current con-
sumption
30 mA max.
Internal power
supply
Voltage range
20.4 to 26.4 VDC (24 VDC
+10%
/
–15%
)
Unit current con-
sumption
110 mA max. (at 24 VDC)
Maximum cur-
rent
0.6 A (with maximum output to I/O Unit)
The capacity required for the internal power supply
of the Communications Unit can be obtained using
the following formula:
Communications Unit internal power supply current
= Communications Unit internal current consump-
tion + total current consumption for the I/O Unit inter-
faces
Inrush current
30 A max.
I/O Unit inter-
face
Number of Units
connected
8 Units max.
Total number of
inputs/outputs
Total inputs (IN) and outputs (OUT): 1,024 points
max.
Rated output
current
0.4 A max.
Overcurrent pro-
tection function
105% of rated current or higher. When an overcur-
rent occurs, the power supply to the I/O Units will
remain OFF until the power supply is turned ON
again.
Noise immunity
±
2000 V
(IEC1000-4-4 via fast transient noise simulator)
Vibration resistance
10 to 150 Hz, 1.0-mm double amplitude or 70 m/s
2
Shock resistance
200 m/s
2
Dielectric strength
500 VAC (between isolated circuits)
Ambient temperature
–10
°
C to 55
°
C
Ambient humidity
25% to 85% (with no condensation)
Operating atmosphere
No corrosive gases
Storage temperature
–25
°
C to 65
°
C
Mounting
DIN 35-mm track
Weight
Approx. 135 g
Safety standards
UL508, CSA22.2
EMC directives
EN50081-2, EN50082-2
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...