154
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
Dimensions
The illustration below shows the GT1-TS04T. The dimensions for the GT1-
TS04P are the same.
Note The vertical center of the Unit is 4.9 mm lower than the center of the DIN
track. The Unit therefore extends downward 41.4 mm (including the mounting
hook) from the DIN track center.
5-3-2
Settings Using the Configurator
Use Ver. 1.20 or later of the DeviceNet Configurator (referred to as the Config-
urator below) to make the following settings and adjustments.
• Setting the input range (page 154)
• Calibrating the Temperature Input Unit (GT1-TS04T: page 158; GT1-
TS04P: page 162)
• Checking accuracy (page 165)
• Clearing calibrated data (page 169)
Input Range Setting
Use the following procedure to set the input range. the DeviceNet and the
MULTIPLE I/O TERMINAL must be connected first.
Note The input range can be set for each point using the Configurator. Ranges can
be set in 4-point units by setting DIP switches.
1,2,3...
1.
Turn ON pin 4 on the DIP switch to enable software settings.
2.
Turn ON the power supply to all the Units of the MULTIPLE I/O TERMINAL,
including the Temperature Input Unit to be set and the Communications
Unit.
3.
Connect the Configurator to the DeviceNet network and go online.
(Unit: mm)
80
Approx. 80
65
37.4
27.6
60
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...