136
Analog Output Units
Section 5-2
Output Status after
Communications Error
Pins 8 and 9 of the DIP switch determine the status of the outputs after a com-
munications error occurs in DeviceNet or I/O Unit interface communications.
When the clear to minimum, clear to maximum, or clear to 0 V setting is used,
the output data is as shown in the following table.
Converted Data
Output the converted data to the Master as shown in the following diagram.
When a negative voltage is to be output, specify the conversion data as the
two’s complement. To obtain a two’s complement from an absolute value, the
NEG instruction is useful.
Conversion Time
The conversion data is refreshed every 4 ms for all 4 points.
Dimensions
Note The vertical center of the Unit is 4.9 mm lower than the center of the DIN
track. The Unit therefore extends downward 41.4 mm (including the mounting
hook) from the DIN track center.
Settings
Output status after communications error
Pin 8
Pin 9
OFF
OFF
Clear to minimum (Clear to the lower limit of the output signal
range.)
OFF
ON
Clear to maximum (Clear to the upper limit of the output signal
range.)
ON
OFF
Clear to 0 V (for –10 to 10 V only)
Clear to minimum (other than the above)
ON
ON
Hold (Maintain previous output status.)
Output signal range
Clear to minimum
Clear to maximum
Clear to 0 V
0 to 5 V
–0.25 V
5.25 V
–0.25 V
1 to 5 V
0.8 V
5.2 V
0.8 V
0 to 10 V
–0.5 V
10.5 V
–0.5 V
–10 to 10 V
–11 V
11 V
0 V
Bit
First word
First word + 1
First word + 2
First word + 3
Output 0 data
Output 1 data
Output 2 data
Output 3 data
(Unit: mm)
Approx. 70
110
60
65
37.4
27.6
4
35
12.6
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...