169
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
Clearing Calibration
If the calibrations fail, clear the calibration data stored in the EEPROM in the
Temperature Input Unit, and restore the Unit to the default values. All the cali-
bration data stored in the Temperature Input Unit will be cleared simulta-
neously.
Use the following procedure to clear the data. The DeviceNet and the MULTI-
PLE I/O TERMINAL must be connected first.
1,2,3...
1.
Turn ON the power supply to all the Units of the MULTIPLE I/O TERMINAL,
including the Communications Unit and the Temperature Input Unit whose
calibration data is to be cleared.
2.
Connect the Configurator to the DeviceNet network and go online.
3.
On the device list for the Configurator, double-click the Communications
Unit to which the Temperature Input Unit is connected.
The Edit Device Parameters Window for the selected Communications
Unit will be displayed.
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...