141
Analog Output Units
Section 5-2
The possible range of offset adjustments depends on the output range. Refer
to the following table.
Note An output range of 4 to 20 mA is possible only with the GT1-DA04.
If the output corresponding to 0% is outside the range of possible adjustments
shown in the above table, check the connection to the output device.
Gain Adjustment
Gain adjustment is used to adjust the rate of fluctuation of output conversion
values so that when the value corresponding to 100% in the output range is
written, it is converted accurately to output 100%. Gain adjustment is used
when the greater the output voltage and output current, the greater the differ-
ence from the actual value due to the features of the Unit or the method of
connection being used.
The possible range of gain adjustments depends on the output range. Refer to
the following table.
Note An output range of 4 to 20 mA is possible with only the GT1-DA04.
Output range
Data corresponding
to 0%
Output
corresponding
to 0%
Adjustment
range
0 to 10 V
0000 Hex (0)
0 V
–0.5 to 0.5 V
–10 to 10 V
F448 Hex (–3000)
–10 V
–11.0 to –9.0 V
1 to 5 V
0000 Hex (0)
1 V
0.8 to 1.2 V
0 to 5 V
0000 Hex (0)
0 V
–0.25 to 0.25 V
4 to 20 mA (See note.) 0000 Hex (0)
4 mA
3.2 to 4.8 mA
Output range
Data corresponding
to 100%
Output
corresponding
to 100%
Adjustment
range
0 to 10 V
1770 Hex (6000)
10 V
9.5 to 10.5 V
–10 to 10 V
0BB8 Hex (3000)
10 V
9.0 to 11.0 V
1 to 5 V
1770 Hex (6000)
5 V
4.8 to 5.2 V
0 to 5 V
1770 Hex (6000)
5 V
4.75 to 5.25 V
4 to 20 mA (See note.) 1770 Hex (6000)
20 mA
19.2 to 20.8 mA
E.g.: Output range is 0 to 10 V
Conversion data
Hexadecimal
(Decimal)
After adjustment
Before adjustment
Voltage
0 V
E.g.: Input range is 0 to 10 V
Conversion data
Hexadecimal
(Decimal)
After adjustment
Before adjustment
Voltage
10 V
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...