162
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
12. When you have completed all the adjustments, click Close.
A message asking if you want to reset will appear. Click Yes. The Commu-
nications Unit and all I/O Units connected to it will be reset, and the Unit
will return to normal operating mode from Calibration Mode. The Edit Unit
Parameters Window for the Temperature Input Unit will be displayed.
Note When calibrating the Temperature Input Unit, the calibration data will
be stored in the Temperature Input Unit and enabled when it is set.
Calibrating the GT1-TS04P
Use the following procedure to calibrate the GT1-TS04P. The DeviceNet and
the MULTIPLE I/O TERMINAL must be connected first.
Note The Temperature Input Unit is correctly calibrated before being shipped from
the factory, and calibration is not necessary for normal operation. Calibrate
the Unit only if absolutely necessary. OMRON is not responsible for the
results of any user-set calibrations. If the manual calibrations fail, clear the
calibration to restore the Unit to the default settings.
1,2,3...
1.
Connect a 6-dial precision resistance box to the Temperature Input Unit
that is to be calibrated.
2.
Turn ON the power supply to all the Units of the MULTIPLE I/O TERMINAL,
including the Temperature Input Unit to be calibrated and the Communica-
tions Unit. Wait approximately 30 minutes until the internal temperature of
the Temperature Input Unit has stabilized.
3.
Connect the Configurator to the DeviceNet network and go online.
DeviceNet network
Communications Unit
Temperature Input Unit
6-dial precision resistance box
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...