24
Specific Example
Section 2-2
b) You must also use the DIP switch and the Configurator to set the
Temperature Input Unit. For details, refer to 5-3 GT1-TS04T and
GT1-TS04P Temperature Input Units.
6.
Connect to the DeviceNet Master Unit.
7.
Turn ON the power.
8.
Set using the Configurator.
Using version 1.11 or later versions of the DeviceNet Configurator, it is
possible, via the network, to set the following:
• Input range for Analog Input Units.
• Output range for Analog Output Units.
• I/O Unit interface error output (low-clear output/high-clear output) for
Analog Output Units.
Note a) When using a DIP switch, the input and output ranges for the An-
alog Input and Output Units can be set in 2-point units, whereas
with a Configurator, a setting can be made for each point.
b) You can set the Temperature Input Unit input range as well as the
I/O Unit settings using the Configurator. For details, refer to 5-3-2
Settings Using the Configurator.
9.
Create the scan list.
Set the Scan List Enable switch (PC software switch) to ON. For example,
for a DeviceNet Master Unit with unit address 0 installed in a C200HX/HG/
Operating specifications
•
Temperature unit
•
Number of decimal places used
•
Enable/disable software settings
Left side of
cassette
•
Input type
•
Input range
Temperature Input Unit
Communications
power supply
DeviceNet Network
Communications
Unit
I/O Unit
24 VDC
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...