Appendix A: Operating Limits
This section outlines the operating limits of the Battery Control Panel.
Exceeding these ratings may damage the system.
Input AC Power Specifications
Symbol
Parameter
Conditions
Min
Typ
Max
Units
V
supply
Supply Voltage
60 Hz
85
120
132
V AC
Supply Voltage
50 Hz
187
240
264
V AC
I
inrush
Inrush Current (Max)
115 V AC
-
-
13
A AC
Inrush Current (Max)
230 V AC
-
-
25
A AC
P
supply
Supply Power
-
-
115
144
W
f
supply
Supply Frequency
-
47
50/60
63
Hz
Ethernet Specifications
Parameter
Min
Typ
Max
Units
Data Speeds
10
-
1000
Base-T
Jack Rating
-
Cat5e
-
-
Cellular Specifications
Parameter
Min
Typ
Max
Units
3G HSPA+ Bands
-
850, 1900
-
MHz
4G LTE Cat 1 Bands
-
B2, B4, B5,
B12, B13
-
-
Data Rate (Up/Down)
-
-
5/10
Mbps
Coverage Area
-
USA, CAN
-
-
Environmental Conditions
Symbol
Parameter
Min
Typ
Max
Units
Thermal Specifications
T
a
Operating Temperature
10
-
40
°C
Storage Temperature
10
-
40
°C
Humidity Specifications
RH
Operating Relative Humidity
25
-
85
%
Storage Relative Humidity
25
-
85
%
Nuvation Energy Battery Control Panel - Product Manual
Document ID: NE-PM-005
85
Rev 1.1, 2020-10-14