Whether the stack is connected or disconnected to the DC bus.
▪
Stack measurements for SOC, voltage and current
6.3.1. Pack Connection/Status
The overall controller operation and connection status is displayed in the upper left corner of the
screen. The behavior of this graphic is the same as described in the dashboard
. A
connect button is available when automatic pack connection has been enabled. When manual
connection of a pack is configured, this connect button is removed.
6.3.2. Stack Enable and Connection
The
connected
and
enable
state of each stack is displayed in the red/green oval. A grey button
labelled
Enable
or
Disable
is located below this status. The button will toggle the enable state of a
stack. When a stack is changed from
enabled
to
disabled
state, the stack is immediately disconnected
from the DC bus. When a non-faulted stack is toggled from
disabled
to
enabled
there will be one of
two possible outcomes
1. If pack auto connection is enabled, the stack is considered a candidate for connecting to the pack.
Refer to
for further details.
2. If manual pack connection is configured, a connect button will appear on the stack status. Refer to
for details of this operation.
6.3.3. Stack Service Lockout
If a stack were to enter its
Service Lockout
state (refer to
Operator Interface Manual: Single-Stack
for
details), the stack status will be updated as shown below.
Nuvation Energy Battery Control Panel - Product Manual
Document ID: NE-PM-005
43
Rev 1.1, 2020-10-14
Curie Update 2