3. Ensure
Persist Configuration to BMS
is checked
Persist Configuration to BMS
Enabling this option tells the controller to persist the imported configuration file.
If you are using known good configuration files you should check this box.
Disabling this option tells the controller to not persist the newly imported
configuration file. On reboot, the controller will revert to the previous
configuration file. This is useful when tweaking and testing configuration files. It
allows you to recover from incorrect configuration settings by rebooting the
controller
Only registers that are prefixed with
pack*
and
gbc*
will be persisted on the
controller.
4. Click
Import Configuration
5. Select the configuration file to use and click
Open
6. A dialog indicating progress will pop-up
7. Wait until a dialog box appears with the configuration import result. It should indicate that the
import was successful.
5.4.2.2. Configuration File Import Troubleshooting
During the configuration file import, if you receive a
Register Write failure error
, ensure you have
valid entries in your configuration file. For details on the various registers and their intended use,
please refer to
If the failures persist, please submit a support ticket with as much detail as possible
to
.
5.4.3. Enable the Stacks
The stacks within the pack need to be
enabled
to allow them to be connected.