6. Click the
Edit
button on the
ip_address
register. This will bring up the
Edit Register
dialog box.
7. Change the IP address according to the constraints discussed in
Write
.
The index field may be left blank for all operations.
8. Confirm that the value has been updated by clicking
Read
.
9. Under the
Manual Register Configuration
panel, expand the row for component name
sc_locked_cfg_persist
.
10. Click the
Edit
button for the
save
register and write a value of
1
.
11. Verify that the configuration has been saved correctly by reading the error register. The value will
be
0
if no errors have occurred.
The network configuration settings have been updated.
Power cycle the Stack Switchgear for the updated network settings to take effect.
Improperly modifying the network settings can result in a Stack Switchgear that
cannot communicate over Ethernet. To restore Stack Switchgear to its default IP
address (192.168.1.21), you must initiate a factory reset action—refer to the
Nuvation Energy Stack Switchgear: Product Manual
for instructions.
Nuvation Energy Battery Control Panel - Product Manual
Document ID: NE-PM-005
22
Rev 1.1, 2020-10-14
Curie Update 2