OM0295
Rev 2 September 2020
Page 12 of 103
5.0
Installation Instructions
5.1 Location
Within the laboratory, pharmacy, etc., the ideal location of the Biosafety cabinet is away from personnel traffic lanes, air
vents (in or out), doors and/or any other source of disruptive air currents.
If drafts or other disruptive air currents exceed the inflow velocity of the cabinet through the access opening, the
potential
exists for contaminated air to exit or enter the work zone area of the cabinet. It depends on the severity of the air current.
REMEMBER: A BIOSAFETY CABINET IS NO SUBSTITUTE FOR GOOD LABORATORY TECHNIQUE.
Where space permits, a clear 6 inch (152mm) area should be permitted on each side of the cabinet for maintenance
purposes. The electrical outlet into which the cabinet is connected should be readily accessible for maintenance purposes.
Do not position the cabinet to prevent access to the power cord.
The power cord plug serves as the disconnect and
should remain readily accessible.
If the outlet is inaccessible, such as a conduit (hardwired) connection, then an appropriate
warning label should be applied near the cabinet's on/off switch, to indicate the circuit breaker on the power distribution
panel to be used.
More than any other Biosafety cabinet, the NU-560 requires careful site-planning and preparation, due to the total exhaust
nature of the cabinet. Proper sizing of the exhaust and make up supply systems are critical to the successful installation of
the cabinet. In addition, the cabinet provides for the choice of make-up air for the supply (downflow) air. The following are
airflow requirements based on concurrent balance values*.
Air Volume (CFM/CMH)
Supply Air
Inflow
Exhaust Air**
NU-560-400
544 / 924
271 / 461
815 / 1385
NU-560-600
865 / 1470
410 / 697
1275 / 2166
*Concurrent Balance Value
is determined by a duct traverse measurement method as specified in ASHRAE Standard 111 at
its nominal setpoint calibrated using the primary DIM method and capture hood removed. These values shall be used for
design and balance exhaust/supply HVAC requirements.
**Exhaust air volume at negative 1.7 inches (43mm) w.g. for NU-560-400
1.8 inches (46mm) w.g. for NU-560-600
Summary of Contents for LabGard NU-560-400
Page 7: ...OM0295 Rev 2 September 2020 Page 7 of 103...
Page 9: ...OM0295 Rev 2 September 2020 Page 9 of 103...
Page 10: ...OM0295 Rev 2 September 2020 Page 10 of 103...
Page 16: ...OM0295 Rev 2 September 2020 Page 16 of 103...
Page 17: ...OM0295 Rev 2 September 2020 Page 17 of 103...
Page 32: ...OM0295 Rev 2 September 2020 Page 32 of 103 Set New Password Retype New Password...
Page 43: ...OM0295 Rev 2 September 2020 Page 43 of 103...
Page 48: ...OM0295 Rev 2 September 2020 Page 48 of 103...
Page 80: ...OM0295 Rev 2 September 2020 Page 80 of 103...
Page 96: ...OM0295 Rev 2 September 2020 Page 96 of 103...
Page 97: ...OM0295 Rev 2 September 2020 Page 97 of 103...
Page 98: ...OM0295 Rev 2 September 2020 Page 98 of 103...
Page 99: ...OM0295 Rev 2 September 2020 Page 99 of 103...
Page 100: ...OM0295 Rev 2 September 2020 Page 100 of 103...
Page 101: ...OM0295 Rev 2 September 2020 Page 101 of 103...