NTI
Mini Server Environment Monitoring System
70
Alert Settings
Disable alerts
Change to “Yes” to prevent alerts from being sent when this sensor’s status changes
Alert Delay
The alert delay is an amount of time the sensor must be in an alert condition before an alert is
sent. This provides some protection against false alarms. The Alert Delay value can be set
for 0-999 seconds or minutes.
Notify Again Time
Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will be
repeated
Notify on Return to Normal
The user can also be notified when the sensor readings have returned to the normal range by
changing to “Yes” for "Notify on return to normal" for a sensor.
Auto Acknowledge
Change to “Yes” to have alert notifications in the summary page return to normal state
automatically when sensor readings return to normal.
Enable Syslog Alerts
Change to “Yes” to have alert notifications sent via Syslog messages
Enable SNMP traps
Change to “Yes” to have alert notifications sent via SNMP traps (v2c)
Enable Email Alerts
Change to “Yes” to have alert notifications sent via Email
Email Subject
Enter the subject to be viewed when an email alert message is received
Attach IP camera capture
Change to “Yes” to enable a snapshot to be taken from an IP camera and attached to the alert
message (for critical alert messages only.)
Selected IP camera
Select which IP camera to take a snapshot from to be attached to an alert message (for critical
alert messages only)
Enable SMS Alerts
Change to “Yes” to have alert notifications sent via SMS (requires GSM modem)
Associated output relay
Choose which output relay to change state when sensor is in alert
Output relay on alert
Choose the state the output relay should be in when the sensor is in alert
Output relay on return
Choose the state the output relay should be in when the sensor returns to normal
Press <
Tab
> to highlight
Save
and press <
Enter
> to save before pressing <
Esc
> to exit.
From the Data Logging menu for the Digital Input
sensor, the user can decide if
the data sampled should be recorded in the Data
Log and how frequently.
Figure 77
- Data Logging for Digital Input Sensors