From the Sensor Settings menu enter the Description for the sensor and select which sensor group the sensor should belong to (1
or 2).
Figure 71- Text Menu-Sensor Settings
Sensor Settings
Description
Description
The description of the sensor that will be viewed in the Summary page and in the body of alert
messages
Group
Assign the sensor to a group (1 -8) (see also page 85)
Units
This lets the operator choose between Celsius and Fahrenheit as the temperature
measurement unit.
Min. Level
Displays the minimum value that this sensor will report
Max. Level
Displays the maximum value that this sensor will report
Minimum Non-Critical
-Threshold
The user must define the lowest acceptable value for the sensors. If the sensor measures a
value below this threshold, the sensor will move to non-critical alert status. The assigned value
should be
¾
within the range defined by Minimum Level and Maximum Level and
¾
lower than the assigned Maximum Threshold value.
If values out of the range are entered, and error message will be shown.
Maximum Non-
Critical Threshold
The user must define the highest acceptable value for the sensors. If the sensor measures a
value above this threshold, the sensor will move to non-critical alert status. The assigned value
should be
¾
within the range defined by Minimum Level and Maximum Level and
¾
higher than the assigned Minimum Threshold value.
If values out of the range are entered, and error message will be shown.
Minimum Critical
Threshold
The user must define the lowest acceptable value for the sensors. If the sensor measures a
value below this threshold, the sensor will move to alert status. The assigned value should be
¾
within the range defined by Minimum Level and Maximum Level,
¾
lower than the assigned Maximum Threshold value, and
¾
lower than the Minimum Non-Critical Threshold value.
If values out of the range are entered, and error message will be shown.
Maximum Critical
Threshold
The user must define the highest acceptable value for the sensors. If the sensor measures a
value above this threshold, the sensor will move to alert status. The assigned value should be
¾
within the range defined by Minimum Level and Maximum Level,
¾
higher than the assigned Minimum Threshold value, and
¾
higher than the Maximum Non-Critical Threshold value.
If values out of the range are entered, and error message will be shown.
Sampling Period
Determines how often the displayed sensor value is refreshed on the Sensor page. A numeric
value and a measurement unit (minimum 1 seconds, maximum 999 minutes) should be entered.
Press <
Tab
> to highlight
Save
and press <
Enter
> to save before pressing <
Esc
> to exit.