NTI
Mini Server Environment Monitoring System
26
Configure Digital Inputs
The configuration page for digital inputs is almost the same as that for temperature and humidity sensors, with a few differences.
Instead of threshold and minimum/maximum levels settings, digital inputs (water sensors and contact sensors) are either open
contact or closed contact sensors. Therefore, the field “Normal Status” is provided to select the status of the sensor when it is
not in an alert state. Select between
Open
contacts, or
Close
contacts for the normal status of the sensor. (Water sensors are
open contact when not in alert state.)
Alert settings and data logging features are the same as those described on page 24.
Figure 21- Sensor Configuration for Digital Inputs
Select between “Open” or “Closed”