P340 - P344E
rEALtimE CLoCk ProgrAmming
ProgrAm moDE LEVEL
Installer, User
FACtory DEFAULt
none
notEs
• The onboard clock is automatically
updated from your cellular network.
you should only need to adjust clock
settings if the panel is being used
'offline' without a SIM card.
• Real Time Clock memory is regularly
saved to non-volatile memory and is
retained on power down.
you should always check the clock
settings on power up and adjust the
time and date if necessary.
These options are used to program the time and date into the Realtime Clock (RTC).
KPX+
PxxxE [New Value] E
NAVIGATOR
PxxxE > [New Value] E
SMS*
P[MasterCode]E P[InstallerCode]E PxxxE [NewValue] E
Or use
NessXCEL
app
P340E
Real Time Clock minutes. Enter a value between 00 and 59. Default 00 minutes.
P341E
Real Time Clock Hours. Enter a value between 00 and 23. Default 00 hours.
P342E
Real Time Clock Day of the month. Enter a value between 01 and 31. Default 01,
(1st day of the month). Ensure that the setting does not exceed the days in the current
month. The panel does not cross-check this setting.
P343E
Real Time Clock Month. Enter a value between 01 and 12. Default 01, (January).
P344E
Real Time Clock year. Enter a value between 00 and 63. (2000–2063). Default 09,
(2009).
P390
AUtotimE WArning PErioD
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
5 minutes
notEs
This option sets the warning period for
all AutoTimers.
rELAtED oPtions
P353E 6E AutoTimer1, keypad beeps
P358E 6E AutoTimer2, keypad beeps
P363E 6E AutoTimer3, keypad beeps
P368E 6E AutoTimer4, keypad beeps
P373E 6E AutoTimer5, keypad beeps
P378E 6E AutoTimer6, keypad beeps
P383E 6E AutoTimer7, keypad beeps
P388E 6E AutoTimer8, keypad beeps
This option enables a keypad beep to warn that an AutoTime action is due to begin.
Set the minutes for the start of the warning period.
The Keypad Beeps option for the required timer/s must also be enabled.
KPX+
P39E [New Value] E
NAVIGATOR
P390E > [New Value] E
SMS*
P[MasterCode]E P[InstallerCode]E P390E [NewValue] E
Or use
NessXCEL
app
The allowed range is 1 to 99 minutes.
P392E 1E
EnAbLE AUtotimE UsEr CoDEs
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
1E OFF
Toggle the current setting for the ENABLING or DISABLING of USER Codes as set by the
AutoTIMERS.
If the USER codes are currently DISABLED but the current AutoTIME period means that
they should be ENABLED then use this option.
KPX+
P392E 1E to enable/disable the option as required
NAVIGATOR
P392E > enable/disable 1E as required
SMS*
P[MasterCode]E P[InstallerCode]E P392E 1E as required
Or use
NessXCEL
app
Option No.
Description
Default Note
P340E
REAL TIME CLOCK SET
minUtEs
00
00–59 minutes
P341E
REAL TIME CLOCK SET
hoUrs
00
00–23 hours
(00=midnight)
P342E
REAL TIME CLOCK SET
DAy
01
01–31 days
P343E
REAL TIME CLOCK SET
month
01
01–12 months
P344E
REAL TIME CLOCK SET
yEAr
09
00–63
(2000–2063)
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
75
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
75
AUtomAtion