P60E 4E
tAmPEr sirEn LoCkoUt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
ON Tamper Reset Lockout enabled.
rELAtED oPtions
P44e
Lockout zones.
This option programs the Tamper input to Lockout, i.e. cause the Siren & Reset outputs to
sound only once while the panel is armed.
KPX+
P60E 4E to enable/disable the option
NAVIGATOR
P60E > enable/disable 4E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 4E
Or use
NessXCEL
app
P60E 5E
DUrEss to rEsEt oUtPUt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF No Reset output on Duress alarm.
rELAtED oPtions
P75e 1e
Enable reporting of Duress.
Keypad Duress is normally a silent alarm. This option makes the Duress alarm trigger the
Reset output. To Disarm with Duress, add any of the digits 5,6,8 or 9 in front of the user
code when Disarming.
KPX+
P60E 5E to enable/disable the option
NAVIGATOR
P60E > enable/disable 5E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 5E
Or use
NessXCEL
app
P60E 6E
AUto ExCLUDE ZonEs
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
ON Auto Exclude enabled.
rELAtED oPtions
P62e 7e
Siren burst on Auto Exclude.
If a zone is unsealed at the end of Exit Time the panel can either Exclude (ignore) that zone
or immediately alarm.
The panel will give a 2 second Siren burst at the end of Exit Time to indicate that the panel
is armed with a zone/s Auto Excluded. The 2 sec Siren burst can be disabled by option
P62E 7E.
KPX+
P60E 6E to enable/disable the option
NAVIGATOR
P60E > enable/disable 6E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 6E
Or use
NessXCEL
app
P60E 7E
DisAbLE kEyPAD DisPLAy
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: Display is always ON.
notEs
• LCD KEYPADS: The LCD display and
display backlighting will turn off but the
key backlighting will remain on. The
keypad flap can be closed to reduce
stray light from the keys.
NAVIGATOR KEyPAD: The touch
screen display will go blank. Touch to
restore.
Keypad displays can be programmed to blank after 4 minutes of no keypad use. Any
action that causes a beep will restore the display. (LCD keypads, use the
button
preferably. Navigator Touch Screen Keypad, touch to restore the display).
KPX+
P60E 7E to enable/disable the option
NAVIGATOR
P60E > enable/disable 7E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 7E
Or use
NessXCEL
app
P60E 8E
DELAyED AUx3 & AUx4 oUtPUts
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: AUX3 & AUX4 outputs are instant.
rELAtED oPtions
P143E 1E, AUX3 on when Area1 arms.
P143E 2E, AUX3 on when Area2 arms.
P144E 1E, AUX4 on when Area1 arms.
P144E 2E, AUX4 on when Area2 arms.
The AUX3 and AUX4 outputs can be programmed to turn on when Areas 1 and 2 are
armed. These outputs can be programmed to turn on instantly or at the end of Exit Time.
This option only applies when AUX3 and AUX4 outputs are enabled as Arm1 and Arm2
outputs, (P143E 1E on and P144E 1E on).
KPX+
P60E 8E to enable/disable the option
NAVIGATOR
P60E > enable/disable 8E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 8E
Or use
NessXCEL
app
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
34
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g