Option No.
Description
Default
P60E
1E
Entry Beeps
ON
2E
Keyswitch Home Monitor/Disarm
OFF
3E
Keyswitch Arm/Disarm
OFF
4E
Tamper Siren lockout
ON
5E
Duress to RESET output
OFF
6E
Auto Exclude zones
ON
7E
Auto keypad display off
OFF
8E
Delayed Aux3, Aux4 outputs
OFF
P60E 1E
Entry bEEPs
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
Entry Beeps ON.
rELAtED oPtions
P69E 7E Arm Exit Beeps.
P69E 8E Home Exit Beeps.
The sonalert will beep during Entry Delay.
KPX+
P60E 1E to enable/disable the option
NAVIGATOR
P60E > enable/disable option 1E
SMS*
P[MasterCode]E P[InstallerCode]E P60E 1E
Or use
NessXCEL
app
P60E 2E, 3E
kEysWitCh oPErAtion
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
Keyswitch disabled.
notEs
The keyswitch:
a/ Always Arms Area1 only.
b/ Does not arm Area2.
c/ Can disarm Area2 if option P120E 8E
is enabled.
• Use a 2K2 resistor on the keyswitch
input regardless of the global EOL
resistor value set by P129E. Also see
P129E, page 73.
• Short the resistor to arm and disarm.
Open circuit to trigger Panic alarm.
rELAtED oPtions
P120E 1E Latched Keyswitch.
P120E 4E Keyswitch Disarms only.
P120E 5E Keyswitch Arms only.
P120E 8E Keyswitch disarm Area2.
P129E EOL Resistor value
An externally fitted, normally open momentary Keyswitch can be used to Arm, Disarm or
arm the Home mode.
The keyswitch is wired to zone 8 (zone 8 is then no longer available as a normal alarm
input, but is still available for use as a Radio Zone).
2E & 3E OFF: No keyswitch operation. Zone 8 is a normal alarm input.
2E ON: Keyswitch cycles between Home and Disarm.
3E ON: Keyswitch cycles between Arm and Disarm.
2E & 3E ON: Keyswitch cycles between Arm, Home and Disarm.
KPX+
P60E enable/disable 2E 3E as required
NAVIGATOR
P60E > enable/disable 2E 3E as required
SMS*
P[MasterCode]E P[InstallerCode]E P60E 2E 3E as required
Or use
NessXCEL
app
p60e 2e is ON
p60e 3e is ON
p60e 2e is ON
p60e 3e is ON
ARMED
ARMED
MONITOR
MONITOR
DISARM
DISARM
DISARM
ARMED
ARMED
MONITOR
MONITOR
DISARM
DISARM
DISARM
p120e 1e is ON
Momentary
Keyswitch
Momentary
Keyswitch
Momentary
Keyswitch
Latching
Keyswitch
KEySWITCH WIRING.
A momentary or latching keyswitch
can be wired as shown.
Always use a 2K2 resistor regardless
of the global EOL resistor value set
by P129E
Optional PANIC BUTTON.
N/C contacts in series.
KEySWITCH
N/O contacts
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
33
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g