Option No.
Description
Default
Note
P83E
TEST CALL INTERVAL
84
x2 = 168hrs
P84E
TIME BEFORE NEXT TEST CALL
none
x2 = 12hrs
P83E
tEst CALL intErVAL
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
84 (=168hrs =7 days).
notEs
• Enter a value from 1 to 99.
rELAtED oPtions
P89E 1E Enable Test Calls.
P84E Time Before Next Test Call.
Test calls to the Central Station can be sent at intervals between 2 and 198 hours in 2 hour
increments. Programmable from 2 to 198 Hours. Enter a value between 1 and 99. (This is
automatically multiplied by 2).
EXAMPLE: To program daily test calls: P83E12E
Test Calls must be enabled by option P89E 1E.
KPX+
P83E [New Time] E
NAVIGATOR
P83E > [New Time] E
SMS*
P[MasterCode]E P[InstallerCode]E P83E [NewTime] E
Or use
NessXCEL
app
P84E
timE bEForE nExt tEst CALL
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
none
notEs
1. Enter a value from 1 to 99.
2. If Test Calls are to start immediately,
then the value is set to 0.
3. The Time Before Next Test Call is
a dynamic value. When viewed, the
current value will be displayed (not the
initially entered value).
rELAtED oPtions
P89E 1E, Enable Test Calls.
P83E, Test Call interval.
instALLEr's tiP
Use P88888888E prior to powering
down for a short time. This will save the
current Time Before Next Test Call and
the Real Time Clock into permanent
memory. On power up these times will
be restored.
This option sets the time before the next test call and is used to set the preferred time for
Test Calls. Programmable from 2 to 198 Hours. Enter a value between 1 and 99. (This is
automatically multiplied by 2).
Examples:
A. New Installation: Set the time before the next test call.
E.g., If you are programming the panel at 5pm and you want test calls to be sent at 1am.
Enter P84E 4E (4 x 2 =8hrs. Therefore 5pm + 8hrs =1am).
B. Existing Installation: To reset the time that test calls are sent.
E.g., Our example panel is sending test calls at 1am and you want to change it to 2am. If
you are programming the panel at 6pm, enter P84E 4E (4 x 2 =8hrs. Therefore 6pm + 8hrs
=2am).
KPX+
P84E [New Time] E
NAVIGATOR
P84E > [New Time] E
SMS*
P[MasterCode]E P[InstallerCode]E P84E [NewTime] E
Or use
NessXCEL
app
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
51