2.4  RATING PLATE INFORMATION

Rating plate is located above and below the domestic hot water inlet and outlet.

W385-0413 / 07.16.10

LISTED SOLID FUEL FIRED CENTRAL FURNACE

 

 

TESTED TO:  

CAN-CSA B366-1-M91 / UL391 4th Ed 2006 (JULY 2008) / UL 727 / CSA B140.4 / CSA B212

MODEL: HMF150

REPORT NO.: _

415-S-09-2 

 

CAUTION:

HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN, CLOTHING AND 
FURNITURE AWAY. CONTACT MAY CAUSE SKIN BURNS. SEE NAMEPLATE AND 
INSTRUCTIONS.

                         TECHNICAL DATA

BLOWER MOTOR 

  1/3 HP

ELECTRICAL RATING 

  120V, 11 AMPS, 60Hz

ELECTRIC FURNACE MODULE  220V, 84 AMPS
EXTERNAL STATIC PRESSURE    0.2” W.C., 0.2” C.E.
DRAFT PRESSURE 

    

WOOD FLUE:   MIN. 0.04“ W.C. TO MAX. 0.06” W.C.
OIL FLUE:   MIN. 0.02” W.C. TO MAX. 0.04” W.C.

OIL FURNACE MAX. FIRING RATE 91,000 BTU INPUT
    AS SHIPPED: - OIL PRESSURE:       120 PSI 

 - NOZZLE:                  0.65 - 60°A 
 - NO. 2 FURNACE OIL

INSTALLATION USE ONLY IN ACCORDANCE WITH WOLF STEEL LTD’S INSTRUCTIONS.  CONTACT LOCAL BUILDING OR FIRE OFFICIALS OR OTHER AUTHORITIES HAVING 
JURISDICTION ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA.

CAUTION:  THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER.

 USE OF UNAUTHORIZED COMPONENTS OR FAILURE TO COMPLY WITH INSTALLA-

TION INSTRUCTIONS WILL RESULT IN VOIDED WARRANTY.

CHIMNEY TYPE

: FOR “WOOD ONLY” FURNACE CONFIGURATION MINIMUM 6” (152mm) DIAMETER LISTED (UL 103HT) RESIDENTIAL CHIMNEY. FOR “WOOD/OIL 

COMBINATION” FURNACE RECOMMENDED MINIMUM 7”(178mm) DIAMETER LISTED (UL 103HT) RESIDENTIAL CHIMNEY.

CHIMNEY CONNECTOR

: 6” (152mm) DIAMETER MINIMUM 24 GAUGE STEEL MINIMUM CLEARANCE FROM HORIZONTAL CONNECTOR AND CEILING 18” (455mm). 

SPECIAL METHODS ARE REQUIRED WHEN PASSING A CHIMNEY THROUGH A WALL OR CEILING. SEE INSTRUCTIONS AND BUILDING CODES.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.  EXCEPTION “ADD ON” CONFIGURATION WITH AN OIL FURNACE REFER TO MANUAL.

DO NOT CONNECT THIS FURNACE TO A CHIMNEY SERVICE A GAS APPLIANCE.

FUEL

: FOR USE WITH SOLID WOOD FUEL ONLY. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. LOAD FUEL CAREFULLY OR DAMAGE MAY 

RESULT.  OIL FURNACE MODULE NO.2 FURNACE  OIL

DANGER:  RISK OF FIRE OR EXPLOSION.

DO NOT ATTEMPT TO LIGHT A FIRE IF THERE IS AN OIL VAPOUR PRESENT.
DO NOT

 USE CHEMICALS OR FLUIDS TO START THE FIRE.

DO NOT

 BURN GARBAGE, GASOLINE, NAPHTA, ENGINE OIL OR OTHER INAPPROPRIATE MATERIALS.

DO NOT

 STORE FUEL OR COMBUSTIBLE MATERIAL WITHIN INSTALLATION CLEARANCES OF THE APPLIANCE.

DO NOT

 USE THIS FURNACE WITHOUT DUCTS – SEE MANUAL FOR ALLOWABLE CONFIGURATION.

WARNING

:

RISK OF SMOKE SPILLAGE. OPERATE ONLY WITH FIRING AND ASHPIT DOOR TIGHTLY CLOSED. DO NOT OVERFIRE. 

IF HEATER OR CHIMNEY CONNECTORS GLOW, YOU ARE OVERFIRING – IMMEDIATELY TURN OFF THERMOSTAT AND 
ENSURE PRIMARY SHUTTER FIRING AND ASHPIT DOOR ARE CLOSED.

CAUTION

:  MAINTAIN COMBUSTION AIR SUPPLY TO BOTH FURNACES.  AIR STARVATION IS DANGEROUS (SEE MANUAL UNDER “OUTSIDE COMBUSTION AIR”.

THE HMF150 FURNACE MAY BE CONNECTED TO DUCTWORK (SUPPLY SIDE – SEE MANUAL) OF ANOTHER FURNACE WHEN USED AS AN WOOD FURNACE “ADD-ON”.

CERTIFIED FOR SERIES CONNECTION TO THE SUPPLY PLENUM OUTLET ONLY OF A GAS FIRED, OIL FIRED, OR ELECTRIC FURNACE.

DO NOT CONNECT DUCTWORK SO THAT REVERSE FLOW IS POSSIBLE.

FOR “ADD ON” INSTALLATION REFER TO MANUFACTURES INSTRUCTIONS FROM ORIGINAL FURNACE FOR INFORMAITON ON MINIMUM DUCT SIZING, ALLOWABLE 
DUCT OPENINGS IN FURNACE CASING AND ELECTRIC DIAGRAMS AND INFORMATION.

DO NOT RELOCATE OR BYPASS ANY OF THE SAFETY CONTROLS IN THE ORIGINAL FURNACE INSTALLATION (“ADD ON” CONFIGURATION).

DO NOT OBSTRUCT SPACE UNDER FURNACE.

 UNIT CAN BE INSTALLED ON COMBUSTIBLE SURFACE (WOOD SUBSTRATE ONLY – CARPET AND OTHER FLOOR 

COVERINGS TO BE REMOVED) PROVIDING EMBER STOP SHIELD (SEE MANUAL) INSTALLED BETWEEN FURNACE AND FLOOR AND MINIMUM 1 ¼” AIR GAP 
MAINTAINED BETWEEN FURNACE AND FLOOR.

INCASE OF POWER FAILURE:  PUSH DOWN ON THE CONTROL ARM OF THE PRIMARY AIR CONTROL AND LOCK IT DOWN USING ROTATING CLASP.  TO AVOID 
EXCESSIVE HEAT BEING TRAPPED IN DUCT WORK ENSURE ALL RETURN AND SUPPLY AIR REGISTERS ARE NOT BLOCKED BY OBJECTS OR DEBRIS AND ALL DUCT 
CONTROL DAMPERS ARE SET OPEN.  SEE MANUAL FOR OPERATION OF WOOD FURNACE IF ELECTRICAL POWER HAS BEEN INTERRUPTED.

OPERATE ORIGINAL FURNACE (ELECTRIC, OIL, GAS) OF A “ADD ON” CONFIGURATION PERIODICALLY TO ENSURE IT WILL OPERATE SATISFACTORILY WHEN NEEDED.

THE HEAT EXCHANGER, FLUE PIPE AND CHIMNEY MUST BE INSPECTED FREQUENTLY AND CLEANED REGULARLY TO REMOVE ACCUMULATED CREOSOTE AND 
ASH. UNDER CERTAIN CONDITIONS OF USE, CREOSOTE BUILDUP MAY OCCUR RAPIDLY. ENSURE THAT THE HEAT EXCHANGER, FLUE PIPE AND CHIMNEY ARE 
CLEANED AT END OF BURNING SEASON, THIS HELPS TO MINIMIZE CORROSION IN THE SUMMER MONTHS. THE APPLIANCE, FLUE PIPE AND CHIMNEY MUST BE 
MAINTAINED IN GOOD CONDITION. UNSAFE TO FIRE WITH WOOD ABOVE TOP OF REFRACTORY BRICK INSIDE COMBUSTIBLE CHAMBER.
USE SUPPLY WIRES SUITABLE FOR 90°C. SEE INSTRUCTION MANUAL FOR ELECTRICAL DIAGRAM.

DANGER

: RISK OF ELECTRICAL SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT.  FOR MORE INFORMATION REFER TO OWNER’S MANUAL.

CAUTION

:  TWO SOURCES OF ELECTRICAL ENERGY PRESENT IN ELECTRIC FURNACE MODULE - DISCONNECT 220V SUPPLY TO MODULE AND 120V SUPPLY TO 

HMF150 FURNACE BEFORE SERVICING.

REPLACE ALL CRACKED OR BROKEN FIRE BRICK AND TOP BAFFLES.  REPLACE GLASS ONLY WITH CERAMIC GLASS.

AUTHORIZED MODULES FOR CONNECTION TO HMF150 FURNACE

:  BLOWER BOX MODULE - 

HMFK-BMP33

, ELECTRIC FURNACE MODULE-

HMFK-EF20, 

OIL FURNACE 

MODULES - 

HMFK-OFRF40

HMFK-OFAFG, 

DHW PREHEAT MODULE - 

HMFK-DHW, 

“ADD ON” KIT - 

HMFK-ADDON

THESE ARE THE ONLY AUTHORIZED COMPONENTS THAT MAY BE ATTACHED TO THE HMF150 FURNACE ASIDE FROM CONNECTION TO FORCED AIR SYSTEM 
RETURN AND SUPPLY PLENUMS. MODULES MUST BE INSTALLED TO MANUFACTURERS INSTRUCTIONS POSTED IN THE INSTALLATION/OWNERS MANUAL ACCOMPA-
NYING HMF150 AND INSTRUCTION ADDENDUMS INCLUDED WITH EACH MODULE.

HMF150 CONFIGURED AS AN “ADD ON”:

MAY BE ADDED ONTO A FURNACE HAVING A RATING AS SHOWN ON THE ORIGINAL NAME PLATE BETWEEN:

‡.:0,1,080$1'.:0$;,080)25(/(&75,&)851$&(

‡0,1,080$1'0$;,08086*3+)252,/)851$&(,1387

‡0$;,080%78+)25*$6)851$&(,1387

REFER TO OWNERS MANUAL

WOLF STEEL 

LTD.

24 NAPOLEON ROAD, BARRIE, ON, L4M 4Y8 CANADA

 

18”

MAX 16”

CLEAR

ANCE T

O

 C

OMBUSIBLES

SER

VICE CLEAR

ANCE

24”

14”

CLEAR

ANCE T

O

 C

OMBUSIBLES

SER

VICE CLEAR

ANCE

24”

LEFT HAND RA CONFIGURATION (REAR VIEW)

MINIMUM 40”

18”

14”

MINIMUM 52”

9”

*Drawing not to scale

OIL FURNA

CE FL

UE

WOOD, WOOD/OIL FLUE

NOTE

‡5()(5720$18$/)255,*+7+$1'&21),*85$7,21&/($5$1&(72&20%867,%/(6

‡7+((/(&75,&)851$&(02'8/(1276+2:1)$//6:,7+,1(19(/23(2)&/($5$1&(72&20%867,%/(6)25:22':22'2,/&21),*85$7,217+(&/($5$1&((19(/23(6'2127

                CHANGE WITH ADDITION OF THE ELECTRIC FURNACE.

CLEAR

ANCE T

O

 C

OMBUSTIBLES

CLEARANCE TO COMBUSTIBLES

48”

18”

24”

1.25”

CLEAR

ANCE T

O

 C

OMBUSTIBLES

SER

VICE CLEAR

ANCE

LEFT HAND RA CONFIGURATION (SIDE VIEW BLOWER MODULE)

9”

*Drawing not to scale

OIL FURNA

CE FL

UE

WOOD, WOOD/OIL FLUE

NOTE:  

SECTION “C” CLEARANCES MAY BE REDUCED TO 0.375” BEYOND A BEND OR 
OFFSET IN THE DUCT SUFFICIENTLY LARGE TO SHIELD THE REMAINDER OF 
THE SUPPLY DUCT FROM DIRECT RADIATION FROM THE FURNACE HEAT 
EXCHANGER.

72”

1”

6”

7 f

t. MINIMUM CEILING HEIGHT

40”

>72”

A

B

C

NOTE:

See 
CAN/CSA-
B365.01 and 
NFPA211 for 
clearance to 
combustible 
specifications 
for return air 
ducting.

CLEARANCE TO COMBUSTIBLES

*Drawing not to scale.

CLEARANCE TO  COMBUSTIBLES

SECTION

A

B

C

TOP

6”

6”

1”

BOTTOM/SIDES

18”

6”

1”

SERIAL

NO.

HMF150

MANUFACTURE DATE:

JAN APR JUL  OCT

FEB MAY AUG NOV

MAR JUN  SEP  DEC

2010 2011 2012 2013

W3

85-0

413

HM

F1

50

LIS

TE

D S

OLID 

FUE

L F

IRED

 C

EN

TR

AL

 F

UR

NA

CE

 

 

TEST

ED

 TO

:  

CA

N-

CSA

 B

366

-1-

M9

1 / 

UL

391

 4t

h E

d 2

00

6 (

JUL

Y 2

00

8) / U

L 7

27

 / C

SA B

14

0.4

 / C

SA

 B

21

2

MOD

EL

: H

MF

15

0

RE

PO

RT N

O.

: _

415

-S-

09

-2_

 

CAUTION

:

HO

T W

HI

LE

 IN

 O

PE

RA

TIO

N. D

O N

OT

 TO

UC

H.

 KE

EP

 CH

ILD

RE

N,

 CL

OT

HI

NG

 AN

D F

UR

NI

TU

RE A

WA

Y. 

CO

NT

AC

T MA

Y C

AU

SE

 SK

IN

 BU

RN

S.

 SE

E N

AM

EP

LA

TE 

AN

D I

NS

TR

UC

TIO

NS

.

     

      

     

     

    T

ECHN

ICAL

 DA

TA

BL

OW

ER 

/ V

EN

TILA

TE

UR  

      

     

     

1/3 HP

EL

ECT

RICAL

 RAT

ING

 /  

       

     

         

120

V, 1

0.3

 AM

PS

AL

IM

EN

TAT

IO

N EL

ECT

RIQUE

        

  6

0Hz

EX

TE

RN

AL ST

ATIC PR

ES

SU

RE

 /   

    0

.2”

 W

.C.

PR

ESS

ION

 ST

ATIQU

E E

XT

.    

     

     

   0

.2”

 C.

E.

DR

AF

T P

RE

SS

UR

E/ 

WOOD

 FL

UE:

     

       

      

     

      

     

  MI

N. 0

.4”

 W

.C

OIL FL

UE:

       

      

     

     

      

     

       

  0.2

”W.

C.

OI

L F

UR

NA

CE

 - OIL

 FI

RIN

G R

AT

E:  

 0.

66

 GA

L US

  - O

IL 

PR

ES

SU

RE:

     

  1

20

 PS

I

- NO

ZZ

LE:

     

     

      

  0.

65 

- 60

°A

INST

AL

LAT

ION

  - U

SE 

ONL

Y IN

 AC

CO

RDA

NCE

 WI

TH

 W

OLF ST

EEL

 LT

D’S I

NS

TRU

CT

IONS

.  C

ON

TA

CT

 LOC

AL 

BU

ILD

ING,

 FIRE

 OFFIC

IAL

S AND

 OT

HE

R AG

ENC

IES 

HA

VIN

G LOC

A

JURISDI

CT

ION

 AB

OUT

 RE

STR

ICTIONS

 AN

D INST

ALLA

TIO

N I

NSPECTION 

IN 

YO

UR

 ARE

A.

CH

IMN

EY

 TY

PE

: FO

R “

WO

OD

 ONL

Y” 

FURN

ACE 

CO

NF

IGUR

AT

ION

 MIN

IMUM

 6”

 (15

2mm

) DIAM

ET

ER 

LIST

ED

 (U

L 1

03HT

) R

ES

IDE

NT

IAL

 CHIM

NE

Y. FO

R “W

OOD

/OIL

 

CO

MBINA

TIO

N” F

UR

NA

CE

 RE

COM

ME

NDE

D M

INIM

UM 7

”(178

mm

) DI

AM

ET

ER 

LISTED

 (UL

 103H

T) 

RE

SID

ENT

IAL

 CHIM

NEY

.

DO

 N

OT

 C

ON

NE

CT TH

IS

 U

NIT

 TO

 A C

HI

MNEY

 FLU

SE

RV

IN

ANO

TH

ER 

AP

PL

IA

NC

E UNL

ES

S US

ING

 IN A

 “A

DD 

ON”

 C

ON

FIGU

RA

TION

 W

ITH A

 PR

EX

IS

ITNG

 O

IL 

FU

RN

AC

- S

EE M

AN

UAL

 U

ND

ER PL

EN

UM 

AN

INS

TA

LLA

TIO

N.

CHI

MNEY

 C

ON

NEC

TO

R

: 6”

 (1

52m

m)

 DIA

ME

TE

R MIN

IMU

M 24

 GA

UGE 

ST

EE

L M

INI

MUM CL

EARA

NCE

 FRO

M HO

RIZO

NT

AL

 CO

NNE

CT

OR A

ND

 CE

ILING 1

8” (45

5m

m). 

SPE

CIAL

 MET

HOD

S A

RE 

RE

QUIRE

D WH

EN

 PA

SS

ING

 A C

HIM

NEY

 TH

ROU

GH A

 WAL

L OR 

CE

ILING

. S

EE

 IN

ST

RU

CT

ION

S A

ND

 BU

ILDI

NG

 CODES.

DO

 N

OT O

BS

TR

UCT S

PAC

UN

DE

R F

UR

NA

CE

.

 UN

IT C

AN

 BE

 INS

TA

LLE

D ON

 CO

MB

UST

IBL

E S

URF

AC

E (W

OOD

 SU

BS

TR

AT

E O

NL

Y –

 CA

RPET

 AN

D O

TH

ER 

FLO

OR 

CO

VE

RIN

GS

 TO

 BE 

RE

MOV

ED) 

PR

OV

IDIN

G E

MB

ER

 ST

OP

 SH

IELD

 (SEE

 MAN

UA

L) 

INS

TA

LLED

 BE

TWEE

N F

URNA

CE

 AN

D FL

OO

R AND 

MIN

IMUM

 1 ¼” 

AIR

 GA

MA

INT

AIN

ED 

BET

WEEN

 FUR

NAC

E A

ND

 FL

OOR

.

FU

EL

: FO

R U

SE

 WI

TH

 SOL

ID WO

OD FUE

L ONL

Y. D

O N

OT 

USE

 GR

ATE

 OR 

EL

EV

AT

E F

IRE

. BU

ILD

 WOOD

 FI

RE

 DIR

EC

TLY

 ON

 HEA

RT

H.

AUT

HORIZE

D MO

DUL

ES

 FO

R CO

NN

EC

TIO

TO

 H

MF

150 F

UR

NA

CE

:

BLO

WER B

OX M

OD

UL

E - 

HMF

K-

BM

P33

ELEC

TRIC FU

RN

AC

E MO

DU

LE

 - 

HMFK

-E

F2

0

OIL

 FU

RN

ACE

 MO

DU

LE

S - 

HM

FK-OF

RF4

0

HM

FK

-O

FA

FG

DHW PRE

HE

AT

 MODU

LE

 - 

HMFK-

DH

W

“AD

D ON

” FU

RN

AC

E MO

DULE

 -

 H

MF

K-

AD

DO

N

TH

ESE

 ARE 

TH

E ON

LY

 AU

THORIZE

D C

OM

PO

NE

NT

S THA

T MA

Y B

E A

TT

AC

HED

 TO

 TH

E H

MF

150

 FURN

ACE 

ASI

DE

 FRO

M C

ON

NE

CT

ION

 TO

 FO

RC

ED

 AIR SY

ST

EM

 

RE

TU

RN

 AND 

SU

PPL

Y PL

EN

UM

S. MODULE

S MU

ST 

BE

 INS

TA

LLE

D T

O M

AN

UF

AC

TU

RERS

 INS

TR

UCTIO

NS

 POS

TED 

IN 

TH

E I

NS

TA

LLAT

ION/O

WNE

RS M

AN

UAL

 

AC

CO

MPA

NY

ING HMF

150

 AN

D IN

STR

UC

TIO

N A

DD

EN

DU

MS

 IN

CLUD

ED

 W

ITH 

EAC

H M

OD

ULE

.

TH

E H

MF15

0 FUR

NA

CE 

IS 

CE

RT

IFIED 

FO

R S

ER

IES

 CON

NE

CT

ION T

O T

HE

 SUPPL

Y P

LEN

UM OU

TL

ET

 ON

LY 

OF

 A GAS 

FIR

ED

, O

IL F

IRED, 

OR

 ELE

CTR

IC 

FU

RN

AC

E W

HE

N

USE

D AS

 AN

 W

OO

D F

UR

NA

CE

 “ADD

-ON

”.

DO

 NO

T CONNEC

T T

HIS

 FU

RN

AC

E T

CH

IM

NE

Y S

ERV

IC

E A

 G

AS 

FU

RN

AC

E.

DO

 N

OT

 CO

NNE

CT

 D

UCTW

ORK S

THA

T R

EVE

RS

FLO

W IS

 P

OSSIB

LE

.

DO

 NO

T RELO

CA

TE OR

 BY

PAS

S A

NY

 O

F TH

E S

AFET

Y C

ONT

RO

LS I

N T

HE O

RI

GIN

AL

 FU

RN

ACE

 INS

TA

LLA

TIO

(”AD

ON”

 C

ONF

IGU

RAT

ION

).

CAUTI

ON

:  THI

S A

PPL

IA

NC

E MU

ST 

BE

 INS

TA

LL

ED

 BY

 A Q

UAL

IFI

ED

 INS

TA

LLER

.

 USE

 OF

 UN

AU

TH

OR

IZE

D CO

MP

ONE

NT

S OR 

FA

ILUR

E TO

 CO

MP

LY

 W

ITH

 

INS

TA

LLA

TION

 IN

STRU

CT

ION

S W

ILL

 RE

SU

LT 

IN 

VO

IDED

 W

AR

RA

NT

Y.

WA

RN

ING

:  RIS

K O

F SM

OK

E S

PIL

LA

GE.

 OP

ERA

TE

 ONL

Y W

ITH 

FIRIN

G A

ND

 AS

H R

EM

OV

AL

 DOOR 

TIG

HT

LY

 CLOS

ED

. DO

 NO

T O

VE

RF

IRE

IF 

HE

ATER OR

 C

HIMN

EY

 CONNECT

OR

GLO

W,

 YO

U AR

OV

ERF

IR

ING 

– IM

ME

DIA

TE

LY

 TURN

 O

FF 

THER

MO

STAT

 AN

D EN

SUR

E P

RI

MAR

Y S

HU

TT

ER

 FI

RIN

G AND 

AS

RE

MO

VA

L DOO

AR

E C

LOS

ED

.

SE

E MA

NUAL

 FO

R O

PE

RA

TION

 OF WOOD

 FURN

AC

E I

F E

LE

CT

RIC

AL 

PO

WE

R HAS BEEN

 INT

ERRU

PT

ED

.

TH

E H

EA

T EXCH

ANGER

, F

LU

E P

IPE

 AN

D C

HIM

NE

Y MUS

T B

E I

NS

PE

CT

ED FRE

QU

EN

TLY

 AN

D CL

EAN

ED

 REG

UL

ARL

Y T

O R

EM

OV

E AC

CUM

ULA

TE

D CR

EO

SOT

E AN

AS

H. U

NDE

R CE

RTA

IN C

ON

DITIONS

 OF USE

, C

REOS

OT

E B

UIL

DU

P M

AY

 OC

CU

R R

API

DLY

. EN

SU

RE

 TH

AT 

TH

E H

EA

T E

XC

HA

NG

ER

, FLU

E PIP

E AN

D C

HIM

NE

Y AR

CL

EA

NED 

AT

 EN

D OF

 BU

RN

ING

 SEASON, T

HIS

 HE

LP

S T

O M

INIM

IZE

 CO

RRO

SIO

N I

N THE

 SU

MM

ER M

ON

THS

. TH

E A

PP

LIA

NC

E, F

LUE

 PI

PE 

AN

D C

HIM

NE

Y M

US

T B

MA

INT

AINE

D IN

 GOO

D CO

ND

ITIO

N. U

NS

AFE

 TO

 FIR

E WIT

H W

OO

D A

BO

VE T

OP

 OF RE

FRA

CTO

RY

 BR

ICK

 INS

IDE

 COM

BU

ST

IBLE CH

AM

BE

R.

REPL

AC

E AL

L CR

AC

KED 

OR

 BRO

KEN

 FIRE 

BR

ICK 

AND

 TO

P B

AFF

LES

.

LO

AD

 FU

EL

 CA

REFUL

LY

 OR

 DA

MAG

E M

AY

 RES

ULT

.

DO

 NOT

 AT

TE

MPT 

TO

 LI

GH

T A

 FIRE 

IF 

TH

ERE 

IS

 A

N O

IL V

AP

OU

R P

RE

SENT

.

DO

 N

OT

 US

E CH

EM

ICA

LS

 OR

 FL

UID

S TO

 ST

AR

T T

HE FIRE

.

DO N

OT

 BURN

 GARB

AG

E, 

GAS

OLINE

, N

APHT

A, E

NGI

NE OI

L OR 

OTHER

 INA

PP

ROPR

IAT

E MA

TERIA

LS.

DO

 NO

T

 ST

OR

E F

UEL

 OR

 CO

MBU

STIB

LE 

MA

TE

RIAL

 W

ITHI

N I

NS

TA

LLA

TIO

N CL

EA

RA

NC

ES

 OF

 THE 

AP

PL

IAN

CE

.

DO NO

T

 USE

 THIS 

FUR

NA

CE

 WIT

HOUT

 DUC

TS – 

SE

E MA

NUAL

 FO

R ALLO

WA

BL

E C

ON

FIG

URA

TIO

N.

CA

UTI

ON:

  US

E S

UP

PLY

 WIR

ES SUIT

ABLE F

OR

 16

7°F

/75

°C.

 SE

E IN

ST

RU

CTI

ON 

MA

NUAL

 FOR

 EL

EC

TR

ICA

L D

IAGR

AM

.

CAU

TIO

N

:  RE

PLA

CE

 GL

AS

S ONL

Y W

ITH

 CE

RAM

IC 

GL

ASS

.

DA

NGER

: R

ISK O

F E

LE

CT

RIC

AL

 SH

OCK

. D

ISC

ON

NECT

 POWE

R BE

FO

RE

 SE

RV

ICIN

G U

NIT

 - D

ISC

ON

NEC

T POWE

R F

ROM

 BO

TH FU

RNA

CE

S I

N A

 “A

DD

 ON

” 

CON

FIGU

RA

TION

.

MA

Y B

E ADD

ED

 ON

TO

 A F

URNA

CE

 HAV

ING

 A RA

TIN

G AS

 SHO

WN

 ON T

HE

 ORI

GIN

AL

 NAM

E P

LAT

E BETWEE

N:

 

‡

 15

 KW 

MINIM

UM AN

D 2

0 K

W MAXI

MU

M F

OR

 EL

EC

TR

IC 

FU

RNA

CE

 

‡

 0.4 M

INI

MU

M AND

 0.6

5 M

AX

IMU

M US

GPH

 FO

R O

IL F

UR

NA

CE

 

‡

 60

,00

0 MI

NIMU

M AN

D 8

0,00

0 MA

XIMUM 

BT

U/H

 FO

R G

AS FU

RNAC

E

CAU

TION

:  M

AINT

AIN COM

BU

ST

ION 

AIR S

UP

PLY

 TO

 BO

TH

 FU

RN

AC

ES

.  A

IR S

TA

RVA

TIO

N I

S D

AN

GEROUS

 (S

EE

 MA

NUAL

 UN

DER 

“OU

TSID

E C

OM

BU

ST

ION

 AIR

”).  

FOR

 “A

DD O

N” INS

TA

LLAT

ION 

RE

FER

 TO

 MA

NUF

ACTURE

S I

NST

RU

CT

ION

S FRO

M ORIGI

NA

L FU

RN

AC

E F

OR

 INFOR

MA

TION

 ON M

INIM

UM 

DU

CT

 SI

ZIN

G, ALLOW

ABLE 

DU

CT

 OPE

NIN

GS

 IN

 FUR

NACE

 CA

SING 

AND 

EL

EC

TR

IC DI

AG

RA

MS

 AN

D I

NF

OR

MAT

ION

.

OPERA

TE

 OR

IGI

NA

L F

URNACE (

EL

ECT

RIC

, O

IL, 

GA

S) 

OF A

 “ADD O

N” C

ON

FIGU

RA

TION 

PE

RIO

DIC

AL

LY TO

 EN

SURE 

IT 

WI

LL 

OP

ERA

TE

 SA

TISF

ACT

OR

ILY

 WHE

N NEEDE

D.

6 ft

6”

1”

1.2

5”

MO

DEL

 N

O.

      

      

SE

RIAL

 NO.

MADE

 IN 

CAN

ADA

 W

ITH D

OM

ESTI

C AN

D I

MP

ORT

ED

 PA

RTS BY

:

W

OLF

 ST

EE

LT

D.

24

 NAP

OL

EON

 RO

AD

, BA

RR

IE, 

ON

, L4M 4

Y8

 CA

NA

DA

 

18

26

26

17

” 

14

” A

ND

 “S

1.2

5”

48”

“S”

14

NO

TE:

“S”

 = 

MINIM

UM

 24”

 SER

VICE

 CL

EA

RANCE

 RE

QU

IRE

D

RE

FE

R T

O S

EC

TION

 6.0

 O

F TH

E IN

ST

AL

LA

TIO

N AN

D O

PERA

TIN

G IN

STR

UC

TIO

N M

AN

UA

L.

W3

85

-04

13

HMF150

LIS

TE

SO

LID 

FUE

FIR

ED

 C

EN

TR

AL

 F

UR

NA

CE

 

 

TE

ST

ED T

O:

  

CA

N-

CS

A B

36

6-1

-M9

1 / 

UL

39

1 4

th

 Ed 2

00

6 (

JU

LY

 20

08

) / 

UL 

72

7 / C

SA B

14

0.4

 / C

SA

 B2

12

MO

DE

L:

 H

MF

150

RE

PO

RT

 N

O.:

 _4

15-

S-09-

2_

 

CAU

TION

:

HO

T W

HI

LE

 IN

 O

PE

RA

TIO

N.

 DO

 NO

T T

OU

CH

. K

EE

P C

HI

LD

RE

N,

 CL

OT

HI

NG A

ND

 FU

RN

ITU

RE

 AW

AY

CONT

AC

T M

AY

 CA

USE

 SK

IN

 BU

RNS

. SE

E N

AM

EP

LA

TE

 AN

D I

NST

RU

CT

ION

S.

     

       

     

      

  TE

CH

NI

CAL

 DA

TA

BL

OWE

R /

 VEN

TILA

TE

UR

     

      

     

  1

/3 

HP

ELE

CTR

ICAL R

AT

IN

G /   

     

       

        1

20V

, 10

.3 

AM

PS,

 

AL

IM

EN

TAT

IO

N EL

EC

TR

IQUE 

         6

0Hz

EX

TER

NA

L S

TA

TIC

 PR

ESSU

RE

 /   

    0

.2” W

.C.

PRE

SS

ION 

ST

ATIQUE

 EX

T.  

     

     

     

0.2”

 C.E

.

DR

AF

T PRES

SU

RE

WOO

D FL

UE

:      

     

     

         

       

    MI

N. 

0.4”

 W

.C

OIL FL

UE

:    

      

     

     

      

     

      

     

 0.

2”W.

C.

OIL F

UR

NA

CE 

- O

IL 

FIRING R

AT

E:  

 0.

66

 GA

L US

  - 

OI

L PRE

SS

UR

E:   

    120

 PS

I

- N

OZZ

LE:

     

     

       

 0.

65 

- 6

0°A

INS

TA

LLA

TIO

N  -

 US

E O

NL

Y IN 

AC

CO

RDA

NC

E W

ITH

 WO

LF STEEL

 LT

D’S I

NS

TRUC

TIO

NS

.  CO

NTA

CT

 LOC

AL

 BU

ILDING

, FI

RE

 OFFI

CIAL

S AND

 OT

HER AGENC

IES 

HA

VIN

G LO

CA

JURISDI

CTI

ON

 AB

OU

T R

EST

RIC

TIO

NS AN

D INS

TA

LLA

TIO

N I

NSPECT

ION

 IN

 YOUR

 ARE

A.

CH

IM

NE

TY

PE

: F

OR

 “WO

OD ONL

Y” FURN

ACE 

CO

NF

IGU

RAT

ION

 MI

NIM

UM

 6”

 (15

2m

m) 

DIAME

TE

R L

IST

ED

 (U

L 1

03H

T) R

ESIDE

NT

IAL

 CHIMN

EY

. F

OR

 “WOOD

/OIL

 

CO

MB

INA

TIO

N” 

FUR

NA

CE

 RECO

MM

EN

DE

D M

INIM

UM 

7”(17

8m

m) DIA

ME

TE

R LI

ST

ED

 (U

L 1

03HT

) RE

SIDE

NT

IAL

 CHIM

NEY

.

DO

 N

OT

 C

ON

NECT

 TH

IS

 U

NIT

 TO

 A CH

IMN

EY

 FL

UE

 SER

VI

NG ANO

TH

ER 

AP

PL

IA

NC

UNL

ESS USING

 IN

 A 

“A

DD

 O

N” 

CO

NF

IG

URA

TIO

N WIT

H A

 P

RE

 E

XI

SI

TNG

 OI

FURNA

CE

 - S

EE 

MA

NUA

L UND

ER P

LE

NUM

 A

ND 

IN

ST

ALL

AT

IO

N.

CHI

MNE

CO

NNE

CT

OR

: 6”

 (1

52mm)

 DIA

ME

TER 

MIN

IMU

M 24

 GA

UG

E S

TEE

L M

INIM

UM

 CL

EA

RA

NC

E FRO

M HORIZO

NTA

L C

ON

NE

CTO

R A

ND

 CE

ILIN

G 1

8” 

(45

5mm

). 

SPE

CIAL

 METH

OD

S A

RE 

RE

QU

IRE

D WH

EN

 PA

SS

ING

 A C

HIM

NE

Y THR

OU

GH A

 WA

LL O

R C

EIL

ING

. SE

E INST

RU

CTI

ON

S AND

 BU

ILDING 

CO

DE

S.

DO

 N

OT

 O

BS

TR

UC

T S

PAC

E U

NDE

R FU

RNAC

E.

 UN

IT 

CA

N B

E INST

AL

LE

D ON

 CO

MB

UST

IBL

E S

URF

AC

E (W

OOD 

SUBSTR

AT

E O

NL

Y – 

CA

RP

ET

 AN

D O

TH

ER

 FL

OOR 

CO

VERIN

GS T

O B

E R

EMOVE

D) 

PR

OVID

ING

 EM

BE

R S

TO

P SHI

ELD

 (SEE

 MAN

UA

L) INS

TA

LLED

 BE

TW

EE

N FURNACE 

AN

D F

LO

OR

 AN

D M

INIM

UM

 1 ¼

” AIR

 GAP

 

MA

INT

AINE

D BET

WEE

N F

URN

AC

E A

ND 

FL

OOR

.

FU

EL

: FO

R U

SE 

WI

TH

 SOLID 

WO

OD

 FUEL

 ON

LY.

 DO

 NO

T U

SE 

GRA

TE

 OR

 EL

EV

AT

E F

IRE

. BU

ILD

 WOO

D F

IRE 

DIRECT

LY 

ON 

HE

AR

TH.

AUTH

ORIZE

D MO

DU

LE

S FO

R CON

NE

CTION

 TO

 HM

F1

50 FU

RNACE

:

BL

OW

ER B

OX M

ODU

LE

 - 

HMF

K-

BM

P33

ELE

CTRIC

 FUR

NA

CE

 MO

DUL

E - 

HM

FK

-E

F20

OIL

 FU

RN

ACE 

MO

DU

LES 

HM

FK

-O

FR

F4

0

HM

FK

-OF

AF

G

DHW 

PR

EH

EAT

 MO

DU

LE

 - 

HMF

K-

DH

W

“ADD

 ON

” F

UR

NAC

E MO

DU

LE

 -

 HM

FK

-A

DDO

N

THE

SE

 ARE 

THE 

ON

LY

 AU

THO

RIZE

D C

OM

PO

NE

NT

S THA

T MA

Y B

E A

TT

AC

HED T

O TH

E H

MF150

 FUR

NACE 

ASI

DE

 FRO

M CON

NE

CTION T

O F

OR

CE

D A

IR SY

ST

EM 

RETU

RN

 AND 

SUP

PL

Y PL

EN

UM

S. MOD

ULE

S M

US

T B

E INS

TA

LLE

D T

O M

AN

UF

AC

TURE

RS

 INS

TRU

CT

ION

S P

OS

TED

 IN TH

E IN

ST

AL

LA

TION/O

WNE

RS M

AN

UAL

 

AC

COM

PA

NY

ING

 HM

F1

50 AND 

INS

TR

UC

TIO

N AD

DE

NDU

MS

 INCLUD

ED 

WIT

H E

AC

H MO

DU

LE

.

TH

E H

MF15

0 FU

RN

AC

E I

S C

ER

TIF

IED 

FO

R S

ER

IES C

ON

NE

CT

ION

 TO

 TH

E S

UPPL

Y P

LE

NU

M O

UT

LE

T ONL

Y O

F A

 GAS

 FI

RED

, O

IL F

IRE

D, 

OR

 EL

EC

TR

IC FUR

NAC

E WH

EN

US

ED

 AS A

N WO

OD

 FUR

NACE

 “ADD

-ON

”.

DO

 NO

T CONN

EC

T THI

S F

URNAC

TO

 A 

CH

IM

NE

Y S

ER

VI

CE

 A G

AS F

UR

NA

CE

.

DO

 NO

T C

ONN

ECT D

UC

TW

OR

K SO

 THA

T RE

VE

RS

FLO

W

 IS 

PO

SSIB

LE.

DO

 N

OT

 R

EL

OCA

TE 

OR

 BYP

AS

S ANY

 O

F TH

E S

AFET

Y C

ONT

RO

LS

 IN TH

OR

IG

INAL

 FURN

ACE I

NST

AL

LA

TIO

(”ADD

 O

N” C

ON

FIGU

RAT

IO

N)

.

CAUTION

:  TH

IS

 A

PPL

IA

NCE

 M

US

T B

INS

TA

LL

ED

 BY

 A 

QU

AL

IFI

ED 

IN

STA

LL

ER

.

 USE

 OF U

NA

UT

HOR

IZE

D CO

MP

ON

ENT

S O

R FA

ILU

RE

 TO

 COM

PL

Y W

ITH

 

INS

TA

LLA

TIO

N I

NS

TRU

CTION

S WIL

L R

ES

UL

T IN

 VOI

DED

 WA

RR

ANTY

.

WA

RNI

NG

:  RISK

 OF

 SMO

KE

 SP

ILL

AG

E. 

OP

ER

AT

E O

NL

Y W

ITH

 FI

RIN

G A

ND

 AS

H RE

MOV

AL

 DO

OR 

TIG

HT

LY

 CLOS

ED.

 DO N

OT

 OV

ER

FIR

E. 

IF 

HE

AT

ER O

CHI

MN

EY

 CO

NN

EC

TO

RS

 G

LOW

, YO

U ARE 

OV

ER

FIR

IN

– IM

ME

DIA

TE

LY

 TU

RN

 O

FF

 TH

ER

MO

STAT

 AND

 E

NS

UR

E PR

IM

ARY

 S

HUTT

ER 

FIR

ING

 AN

AS

REM

OV

AL

 D

OO

R A

RE

 C

LO

SE

D.

SEE

 MA

NUAL

 FOR OP

ERA

TION

 OF WO

OD

 FU

RNAC

E IF

 ELE

CT

RIC

AL P

OWE

R H

AS

 BEEN INT

ERR

UP

TE

D.

THE

 HE

AT

 EXC

HAN

GE

R, FLU

E PIP

E A

ND

 CH

IMN

EY

 MUS

T BE INS

PEC

TE

D F

REQ

UE

NTL

Y AN

D CL

EA

NE

D RE

GU

LA

RL

Y T

O R

EM

OV

E A

CC

UM

UL

AT

ED

 CREO

SO

TE 

AN

AS

H. U

ND

ER

 CE

RT

AIN 

COND

ITION

S O

F US

E, CRE

OS

OT

E B

UIL

DUP

 MAY

 OCCU

R R

AP

IDLY

. E

NSU

RE

 THA

T TH

E H

EA

T E

XC

HA

NG

ER,

 FLU

E P

IPE 

AN

D C

HIM

NEY

 AR

CLEA

NED A

T E

ND

 OF

 BUR

NIN

G SEA

SON, 

TH

IS HE

LP

S T

O M

INIM

IZE CO

RR

OS

ION I

N THE

 SU

MM

ER

 MO

NTH

S. T

HE 

AP

PL

IAN

CE,

 FL

UE

 PI

PE

 AND C

HIMN

EY

 MU

ST B

MA

INT

AIN

ED 

IN G

OOD 

CO

ND

ITION.

 UN

SA

FE 

TO

 FIRE

 W

ITH

 W

OOD 

ABO

VE T

OP

 OF

 RE

FR

AC

TO

RY

 BR

ICK

 IN

SIDE

 COM

BUS

TIB

LE CH

AMB

ER.

RE

PL

ACE

 AL

L C

RA

CK

ED

 OR

 BR

OKE

N FIR

E B

RIC

K A

ND 

TO

P B

AF

FLE

S.

LO

AD

 FUEL

 CA

RE

FU

LLY

 OR D

AM

AG

E M

AY

 RE

SUL

T.

DO

 N

OT

 AT

TE

MPT 

TO

 LI

GHT

 A 

FIR

E IF

 THER

E IS

 A

N OI

L V

AP

OU

PRE

SENT

.

DO

 NOT

 US

E C

HE

MICA

LS

 OR

 FL

UID

S T

O S

TA

RT

 TH

E F

IRE.

DO

 N

OT

 BURN G

AR

BA

GE

, G

ASO

LINE, 

NA

PHT

A, ENGIN

E O

IL OR O

THE

R I

NAPP

ROP

RIA

TE

 MA

TE

RIA

LS.

DO

 N

OT

 STO

RE

 FUE

L O

R CO

MB

UST

IBLE

 MAT

ER

IAL 

WI

THIN IN

ST

AL

LA

TION 

CL

EA

RA

NCES

 OF

 TH

E A

PP

LIAN

CE.

DO 

NO

T

 USE

 TH

IS F

URN

AC

E W

ITHOUT

 DUC

TS

 – S

EE

 MAN

UA

L F

OR 

AL

LO

WAB

LE

 CONF

IGU

RA

TIO

N.

CAU

TIO

N:

  U

SE

 SUP

PLY

 W

IRE

S S

UIT

ABL

E F

OR

 167°F

/75°C

. SE

E INS

TR

UCT

ION 

MA

NU

AL F

OR

 EL

EC

TR

ICA

L D

IAGR

AM

.

CA

UT

IO

N

:  RE

PL

ACE

 GL

ASS

 ON

LY

 W

ITH

 CER

AM

IC G

LA

SS.

DA

NGE

R

: R

ISK

 OF

 EL

EC

TR

ICAL

 SH

OC

K. DI

SC

ON

NE

CT

 PO

WER B

EF

ORE

 SE

RV

ICING UNIT

 - D

ISC

ONN

ECT

 PO

WE

R F

RO

M B

OTH FU

RNAC

ES

 IN

 A “

ADD

 ON

” 

CON

FIGUR

AT

ION

.

MAY

 BE 

ADDE

D ONT

O A

 FU

RN

ACE

 HA

VIN

G A R

AT

ING

 AS 

SHO

WN

 ON TH

E O

RIG

INAL

 NAM

E PL

AT

E BET

WE

EN:

 

‡

 15

 KW

 MIN

IMUM 

AND 

20 

KW 

MAXI

MU

M F

OR E

LE

CTRI

C FU

RN

AC

E

 

‡

 0.4

 MIN

IMU

M A

ND

 0.65 

MA

XIMUM

 US

GP

H F

OR OI

L F

UR

NA

CE

 

‡

 60,

000

 MI

NIMU

M AN

D 8

0,000 

MA

XIMUM

 BT

U/H 

FOR

 GA

S FU

RNACE

CA

UTION

:  M

AIN

TAIN 

CO

MBU

ST

ION 

AIR S

UPP

LY 

TO

 BO

TH

 FUR

NA

CE

S. 

 AI

R S

TA

RVA

TIO

N IS 

DA

NG

EROUS (

SE

E M

AN

UA

L U

ND

ER 

“OU

TS

IDE 

COM

BU

ST

ION A

IR”

).  

FO

R “AD

D O

N” 

INST

AL

LA

TION R

EFER T

O MA

NU

FA

CTU

RE

S I

NS

TR

UC

TION

S F

ROM 

OR

IGI

NAL

 FU

RN

AC

E FOR

 IN

FO

RM

AT

ION

 ON

 MI

NIM

UM

 DU

CT 

SIZ

ING

, A

LLOW

AB

LE 

DU

CT

 OPE

NINGS

 IN

 FU

RN

ACE 

CA

SIN

G A

ND

 EL

EC

TR

IC D

IAG

RAM

S A

ND

 IN

FO

RMA

TIO

N.

OP

ERA

TE

 OR

IGIN

AL F

URN

AC

E (

EL

EC

TR

IC,

 OIL

, G

AS) 

OF

 A “ADD

 ON

” C

ON

FIG

UR

ATI

ON

 PER

IODI

CA

LLY 

TO

 ENSU

RE

 IT

 W

ILL

 OPE

RAT

E S

ATI

SF

AC

TO

RIL

Y W

HE

N N

EE

DE

D.

6 f

t

6”

1”

1.2

5”

MOD

EL

 NO.

      

      S

ER

IA

L N

O.

MA

DE 

IN C

AN

AD

A WI

TH

 DOM

ESTIC

 AN

D I

MPOR

TE

D P

AR

TS BY

:

WO

LF

 STE

EL 

LT

D.

24

 NAP

OL

EO

N RO

AD

, B

ARR

IE, 

ON, 

L4M

 4Y

8 C

ANA

DA

 

18

26”

26”

17

” 

14

” A

ND

 “S

1.25”

48”

“S”

14

NO

TE:

“S”

 = M

INIM

UM

 24”

 SER

VICE

 CL

EA

RA

NC

E RE

QU

IRE

D

REF

ER

 TO

 SE

CT

ION

 6.0

 O

F T

HE

 INS

TA

LLA

TION

 AN

OP

ERA

TIN

G IN

ST

RU

CT

IO

N M

ANU

AL

.

Summary of Contents for HYBRID 150

Page 1: ...TO BOTH FURN ACES AIR STAR VATIO N IS DANG EROU S SEE MANU AL UNDE R OUTS IDE COMB USTIO N AIR FOR ADD ON INSTA LLATI ON REFE R TO MANU FACT URES INSTR UCTIO NS FROM ORIG INAL FURN ACE FOR INFOR MATI...

Page 2: ...GENERAL PLENUM AND DUCTING CLEARANCE TO COMBUSTIBLES 41 6 4 FLUE CONFIGURATION FOR ADD ON FURNACE CONFIGURATION 41 6 5 CONNECTING DUCTWORK PLENUMS BETWEEN ADD ON FURNACE AND ORIGINAL FURNACE 42 6 6 E...

Page 3: ...T SIZING ALLOWA BLE DUCT OPENIN GS IN FURNAC E CASING AND ELECTR IC DIAGRA MS AND INFORM ATION OPERAT E ORIGINA L FURNAC E ELECTR IC OIL GAS OF A ADD ON CONFIG URATIO N PERIOD ICALLY TO ENSURE IT WILL...

Page 4: ...r and free from combustible materials gasoline and other flammable vapors and liquids Under no circumstances should this appliance be modified Do not use this appliance if any part has been under wate...

Page 5: ...ANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED CHILDREN AND PETS MUST BE KEPT FROM TOUCHING THE APPLIANCE WHEN IT IS HOT CONTACT YOUR LOCAL AUTHORIZED DEALER DISTRIBUTOR FOR SAFETY...

Page 6: ...W415 0910 A 09 16 10 6 AIR FLOW CIRCULATION AND HEAT TRANSFER COMBUSTION AIR FLOW...

Page 7: ...city Choice of glass door for radiant heat through front of furnace or solid door to provide more heating through exchange surfaces Firebrick lining for firebox creates kiln like temperatures for maxi...

Page 8: ...FAFG DHW PREHEA T MODULE HMFK DH W ADD ON FURNAC E MODULE HMFK AD DON THESE ARE THE ONLY AUTHOR IZED COMPON ENTS THAT MAY BE ATTACHE D TO THE HMF150 FURNAC E ASIDE FROM CONNEC TION TO FORCED AIR SYSTE...

Page 9: ...USTION AIR DO NOT DRAW AIR FROM GARAGE SPACES EXHAUST PRODUCTS OF GASOLINE THE COMBUSTION ENGINES ARE HAZARDOUS DO NOT DRAW AIR FROM ATTIC SPACES BASEMENTS OR ABOVE THE ROOFING WHERE OTHER HEATING APP...

Page 10: ...IC PRESSUR E 0 2 W C 0 2 C E DRAFT PRESSUR E WOOD FLUE MIN 0 04 W C TO MAX 0 06 W C OIL FLUE MIN 0 02 W C TO MAX 0 04 W C OIL FURNACE MAX FIRING RATE 91 000 BTU INPUT AS SHIPPED OIL PRESSUR E 120 PSI...

Page 11: ...located so they can not be blocked i e snowdrifts 4 above grade or above maximum snow grade for the area is recommended Make a 6 inch hole to suit in an outside wall of the house From outside place t...

Page 12: ...E PALLET IS SECURED TO THE FURNACE BY ADJUSTING THE LEGS AT THE BOTTOM OF THE FURNACE THE BASE PALLET SHOULD NOT BE REMOVED UNTIL THE FURNACE IS PLACED CLOSE TO ITS FINAL INSTALLATION LOCATION LIFTING...

Page 13: ...tipping the skid STEP 2 Firmly support side of the furnace near top to prevent furnace toppling when the skid furnace are tilted HIGH CENTRE OF GRAVITY 2ND INSTALLER SUPPORTS WEIGHT OF UNIT FROM TOP...

Page 14: ...ARE REVERSIBLE STEP 1 Remove all screws holding side panels STEP 2 Tilt side panels outwards from top and pull up diagonally STEP 3 Switch panels to opposite sides and reverse process Attach the elect...

Page 15: ...s 12 pan head screw x8 to mounting the brackets LEFT RA RIGHT RA 4 6 MOUNTING PRIMARY AIR CONTROL LEFT HAND RA Location of the Primary Air Control in left and right RA IMPORTANT This step must follow...

Page 16: ...as illustrated using the fasteners supplied ENSURE CORRECT ORIENTATION OF SHUTTER AS SHOWN ON TOP ON BOTTOM Main air control box is secured with 3 screws into the rear panel and 1 through the inside...

Page 17: ...h gap along the front This will allow the flue gases to escape the firebox Spread the baffles tight to each side to ensure there are not gaps as illustrated STEP 5 Continue to install the front tube p...

Page 18: ...CHIMNEY AND THE SURROUNDING ENCLOSURE J J K K A A A A A A A A A A A A A A A A A A A A A A A B B C C C H D D E E F F G I I DOOR HANDLE DOOR SPRING WASHER SPACER DOOR HANDLE LATCH LOCK WASHER NUT NOTE...

Page 19: ...tion 5 3 Hybrid HMF150 as a Combination Wood Electric Furnace see Section 5 4 Hybrid HMF150 as a Combination Wood Oil Electric Furnace see Section 5 5 5 0 CONFIGURATION OF LEFT AND RIGHT RA WITH OTHER...

Page 20: ...e any of the safety controls in the original furnace installation 6 Maintain sufficient combustion air supply to both furnaces Air starvation is dangerous see Section 3 2 Outside Combustion Air 7 Refe...

Page 21: ...ation blower 14 Do not connect under any circumstances to the chimney or vent serving a gas furnace or gas appliance 15 Disconnect power from both electric furnace and Add On furnace before servicing...

Page 22: ...enum by lining up the clearance holes in the lower switch bracket and the pilot holes in the furnace top secure with hex head screws Secure the top flange of the switch mounting bracket by fastening w...

Page 23: ...OL WILL AFFECT THE OPERATING EFFICIENCY OF THE FURNACE AND WILL VOID THE WARRANTY COVERAGE Once set point limits have been confirmed carefully manipulate wiring inside wood limit connection box so tha...

Page 24: ...otor speed when operating Add On should provide an airflow of 1100 1300 CFM thru the ducting system NOTE Instructions and specifications to be included in kit for a ECM motor in original furnace relay...

Page 25: ...anges align with pilot holes on side of the furnace panel STEP 7 Lift the blower exhaust side of blower box so as to allow mounting flange on the bottom edge of the blower box to clear the top edge of...

Page 26: ...AND FLOOR FAILURE TO COMPLY MAY RESULT IN ELECTRIC SHOCK FIRE PROPERTY DAMAGE OR PERSONAL INJURY STEP 10 See SECTION 7 0 ELECTRICAL CONNECTIONS AND SCHEMATICS STEP 9 See SECTION 6 0 PLENUM AND VENTING...

Page 27: ...ow Steps 1 to 9 from SECTION 5 2 HYBRID HMF150 AS A STAND ALONE WOOD FURNACE LEFT HAND RA RIGHT HAND RA STEP 10 Remove the contents of the Oil Furnace Module Kit HMFK OFRF40 or HMFK OFAFG and compare...

Page 28: ...OMING FROM THE BLOWER MODULE INCORRECTLY ASSEMBLED OIL FURNACE COMPONENTS CAN RESULT IN POOR PERFORMANCE AS WELL AS COMPONENT AND OR PROPERTY DAMAGE AIR FLOW DIRECTION FROM BLOWER MODULE HEAT EXCHANGE...

Page 29: ...WN SIGHT GLASS BRACKET GASKET SIGHT GLASS FLANGE GASKET FURNACE BOTTOM OIL FURNACE COMBUSTION CHAMBER FIREBOX FRONT ALL 115V ELECTRICAL PRE ASSEMBLED HARNESSES MUST BE INSTALLED AS PER INSTRUCTIONS NO...

Page 30: ...appropriate bulk head on frame of oil burner and the flex conduit shielding secured to the bulk head by the 90 flex connector Connector should be secured from other side of bulk head by connector nut...

Page 31: ...lock nut from within box Connect the wires from the oil limit wire harness to the oil limit terminals as per Figure A Secure all the flag connectors to the switch terminals and route the ground line t...

Page 32: ...ue pipe Secure the 5 flue plate to the rear panel using hex head self drilling screws 9 pcs NOTE Clearance holes in the 5 flue plate cover may not align perfectly with the original pilot holes in rear...

Page 33: ...using 1 4 hex head self drilling screws LEFT HAND RA CONFIGURATION TOP FLANGE OF HEAT SHIELD RESTS ON BOTTOM OF OIL FURNACE FLUE PIPE HORIZONTAL LEG OF HEAT SHIELD CLOSEST TO FLUE PIPE BOTTOM OF LOWE...

Page 34: ...tems are more typical where piping lengths are excessive or suction lines start below the level of the oil burner For more detail on which method is more suited for a particular installation see appro...

Page 35: ...7 Remove contents of the electric furnace module kit and compare with contents list on manual addendum accompanying the electric furnace module STEP 8 Place the blower module and the electric furnace...

Page 36: ...lex connector should also be passed through and secured by connector nut on the inside of box BLOWER SIDE PANEL BLOWER HARNESS LOWER ELECTRICAL BOX TO BLOWER MODULE ALL ELECTRICAL WIRING AND CONNECTIO...

Page 37: ...n Connect the single pair 24V control wire not supplied to the Electric Furnace terminals on the terminal strip mounted to top of the main control box Route and secure the control wire around the back...

Page 38: ...7 from SECTION 5 4 HYBRID HMF150 AS A COMBINATION WOOD ELECTRIC FURNACE STEPS 8 19 Follow Steps 2 to 12 from SECTION 5 3 HYBRID HMF150 AS A COMBINATION WOOD OIL FURNACE STEPS 21 See SECTION 7 0 ELECTR...

Page 39: ...G APPLIANCES 2100 F VENTING CONFIGURATION FOR BRINGING SEPARATE WOOD AND OIL FURNACE FLUES INTO A COMMON VENT 1 2 3 4 11 10 9 8 7 6 5 12 1 2 3 4 10 9 8 7 6 5 11 12 Legend ITEMS 1 THROUGH 11 BY INSTALL...

Page 40: ...NCE TO COMBUSTIBLES 48 18 24 1 25 CLEARANCE TO COMBUSTIBLES SERVICE CLEARANCE RIGHT HAND RA CONFIGURATION SIDE VIEW BLOWER MODULE Drawing not to scale CLEARANCE TO COMBUSTIBLES 9 OIL FURNACE FLUE WOOD...

Page 41: ...1 BOTTOM SIDES 18 6 1 Separate chimneys are required when connecting the HMF150 to a pre existing natural gas or propane furnace 6 4 FLUE CONFIGURATION FOR ADD ON FURNACE CONFIGURATION UNDER NO CONDI...

Page 42: ...F THE CENTRA ORIGINAL FURNACE FAILURE TO COMPLY MAY RESULT IN DAMAGE TO PROPERTY AND CREATE A FIRE HAZARD FOR MORE INFORMATION ON ALLOWABLE PROHIBITED METHODS OF CONNECTING ADD ON FURNACES TO A PRE EX...

Page 43: ...DD ON WOOD FURNACE HORIZONTAL EXISTING FURNACE H For installations on combustible flooring an ember stop protective floor covering must be installed An ember stop of minimum 0 015 thick sheet metal ex...

Page 44: ...2 I Green J Ground screw in electric box Wiring connections to fan control in electric furnace module K Red L Red 7 0 ELECTRICAL CONNECTIONS AND SCHEMATICS 7 1 BLOWER BOX WIRING CONNECTIONS ALL ELECT...

Page 45: ...RODUCTS HMF150 CONTROLS CIRCUITRY DIAGRAM ADD ON FIELD WIRING JUNE 3 2010 A 3 2 N 12 120V 24V R G B C TOGGLE SWITCH 1 2 3 4 5 6 7 8 9 10 11 12 TT D E F C1 C2 IMPORTANT FIELD INSTALLATION NOTES A MOVE...

Page 46: ...2 3 4 9 10 13 5 6 7 8 11 12 14 15 16 AIR DAMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V NAPOLEON PRODUCTS HMF150 CONTROLS CIRCUITRY DIAGRAM WOOD ONLY FIELD WIRING JUNE 3 2010 A TOGGLE SWITCH 1 2 3 4 5...

Page 47: ...AMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V NAPOLEON PRODUCTS HMF150 CONTROLS CIRCUITRY DIAGRAM WOOD ELECTRIC FIELD WIRING JUNE 3 2010 A TOGGLE SWITCH 1 2 3 4 5 6 7 8 9 10 11 12 E F CIRCULATION FAN...

Page 48: ...15 16 AIR DAMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V NAPOLEON PRODUCTS HMF150 CONTROLS CIRCUITRY DIAGRAM WOOD OIL FIELD WIRING JUNE 3 2010 TOGGLE SWITCH 1 2 3 4 5 6 7 8 9 10 11 12 E F CIRCULATION...

Page 49: ...5 JUMPER 11B 10B N 1 3 2 24 VAC R G COM 120 VAC L1 N OIL 1 2 3 4 9 10 13 5 6 7 8 11 12 14 15 16 AIR DAMPER MOTOR WOOD THERMOSTAT 120V 120V 24V 24V NAPOLEON PRODUCTS HMF150 CONTROLS CIRCUITRY DIAGRAM W...

Page 50: ...ary air control box a control arm and handle protrudes out To increase combustion push down on this handle moving it towards the bottom of the clearance slot keep the rod down by swinging the clasp al...

Page 51: ...TION DURING THE HEATING SEASON FAILURE TO COMPLY WITH THIS WILL RESULT IN EXCESSIVE CHILLING OF THE EXHAUST PRODUCTS AS THEY PASS THROUGH THE EXCHANGER PIPES THE FURNACE FLUE AND THE CHIMNEY SYSTEM TH...

Page 52: ...create a large quick burning fire use small pieces of wood For a lower but extended burn stack larger pieces of wood close together For long burns leave a 1 2 bed of ashes for best secondary burn perf...

Page 53: ...y after refuelling will reduce the firebox temperature and may result in an unsatisfactory burn As soon as the doors are closed you may if glass door is installed observe a change in the flame pattern...

Page 54: ...ass damper and then slowly open the door to prevent smoke spillage Use a pair of long appliance gloves when feeding the fire Keep a small steel shovel nearby to use as a poker and to remove ashes Do n...

Page 55: ...D CAUSE THE FURNACE TO OVER FIRE THIS COULD RESULT IN DAMAGE TO THE FURNACE PROPERTY DAMAGE OR PERSONAL INJURY IMPROPER DISPOSAL OF ASHES RESULT IN FIRES DO NOT DISCARD ASHES IN CARDBOARD BOXES DUMP I...

Page 56: ...ay with a fire extinguisher or water from a garden hose 4 Do not operate the appliance again until you are certain the chimney has not been damaged 9 1 RUN AWAY OR CHIMNEY FIRE 9 0 MAINTENANCE All hom...

Page 57: ...igh more per cord and burn a little slower and longer Firewood should be split and stacked in a manner that air can get to all parts of it and covered in early spring to be ready for burning that fall...

Page 58: ...e screws and brackets holding the glass in place Remove all broken glass 9 6 3 Wrap the edges of the new glass with a U shaped strip of fiberglass gasket covering 1 4 on each side 9 6 4 Place the glas...

Page 59: ...ION AND REMOVAL When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote These vapors condense in the relatively cooler chimney flue of...

Page 60: ...DOOR GASKET MAINTENANCE It is important to maintain the door gasket in good condition After a while the gasket might sag requiring replacement 9 11 CARE OF GLASS IF EQUIPPED If the glass is not kept c...

Page 61: ...RTY DAMAGE OR PERSONAL INJURY WARNING APPLIANCE AND ACCESSORY REPLACEMENT PARTS PART NUMBER DESCRIPTION W300 0017 DOOR GLASS CERAMIC DOOR SOLID INSERT ASSEMBLY DOOR GASKET DOOR GLASS GASKET W090 0015...

Page 62: ...r the home Adding more pipe or a draft inducing cap may help See the section on Selecting Wood for details Chimney height and outside conditions can negatively affect draft In these cases a small amou...

Page 63: ...such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be cause...

Page 64: ...W415 0910 A 09 16 10 64 13 0 SERVICE HISTORY...

Page 65: ...W415 0910 A 09 16 10 65 14 0 NOTES...

Page 66: ...W415 0910 A 09 16 10 66 14 0 NOTES...

Page 67: ...AND 20 KW MAXIM UM FOR ELEC TRIC FURN ACE 0 4 MINIM UM AND 0 65 MAXIM UM USGP H FOR OIL FURN ACE 60 00 0 MINIM UM AND 80 00 0 MAXIM UM BTU H FOR GAS FURN ACE CAUT ION MAIN TAIN COMB USTIO N AIR SUPP...

Page 68: ...N E BOIS ET HUILE 39 6 3 PL NUM ET SYST ME DE CONDUITS D GAGEMENTS AUX MAT RIAUX COMBUSTIBLES 41 6 4 CONFIGURATION DE L VACUATION DANS LE CAS D UNE FOURNAISE ANNEX E 41 6 5 RACCORDEMENT DES CONDUITS P...

Page 69: ...NUFA CTURES INSTRUC TIONS FROM ORIGINA L FURNAC E FOR INFORM ATION ON MINIMUM DUCT SIZING ALLOWA BLE DUCT OPENING S IN FURNAC E CASING AND ELECTR IC DIAGRAM S AND INFORM ATION OPERAT E ORIGINA L FURNA...

Page 70: ...n raison des peluches provenant des tapis literie etc L emplacement de l appareil doit tre gard libre de tous mat riaux combustibles essence ou autres liquides et vapeurs inflammables Cet appareil ne...

Page 71: ...APPAREIL CET APPAREIL EST CHAUD LORSQU IL FONCTIONNE ET PEUT CAUSER DE GRAVES BR LURES EN CAS DE CONTACT IL FAUT EMP CHER LES ENFANTS ET LES ANIMAUX DE TOUCHER L APPAREIL QUAND IL EST CHAUD CONTACTEZ...

Page 72: ...W415 0910 A 09 16 10 6 CIRCULATION D AIR ET CHANGE DE CHALEUR CIRCULATION DE L AIR COMBURANT...

Page 73: ...fournaise permettant une chaleur rayonnante ou une porte pleine permettant une plus grande distribution de la chaleur travers le syst me de conduits de la maison Les briques r fractaires recouvrant la...

Page 74: ...EN TIAL CHIMNEY DO NOT CONNEC T THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHE R APPLIAN CE UNLESS USING IN A ADD ON CONFIGU RATION WITH A PRE EXISITNG OIL FURNAC E SEE MANUAL UNDER PLENUM AND INSTALL ATI...

Page 75: ...Z PAS LA PRISE D AIR EXT RIEUR DANS LE GARAGE LES PRODUITS D CHAPPEMENT PROVENANT DES MOTEURS ESSENCE SONT DANGEREUX N INSTALLEZ PAS LA PRISE D AIR EXT RIEUR DANS UN GRENIER UN SOUS SOL OU AU DESSUS D...

Page 76: ...WOOD FLUE MIN 0 04 W C TO MAX 0 06 W C OIL FLUE MIN 0 02 W C TO MAX 0 04 W C OIL FURNACE MAX FIRING RATE 91 000 BTU INPUT AS SHIPPED OIL PRESSUR E 120 PSI NOZZLE 0 65 60 A NO 2 FURNACE OIL INSTALLA TI...

Page 77: ...neige il est conseill de les installer comme suit 4 au dessus du sol ou du niveau maximal d accumulation de neige selon la r gion Faites un trou de 6 dans un mur ext rieur de la maison De l ext rieur...

Page 78: ...uincaillerie AVERTISSEMENT LA FOURNAISE EST FIX E LA BASE DE LA PALETTE PAR L INTERM DIAIRE DES PIEDS D AJUSTEMENT LA BASE DE LA PALETTE NE DEVRAIT PAS TRE ENLEV E AVANT D AVOIR PLAC LA FOURNAISE PR S...

Page 79: ...ette TAPE 2 Soutenez solidement le c t de la fournaise pr s du haut afin d viter qu elle bascule lorsque la palette fournaise est inclin e CENTRE DE GRAVIT LEV LE DEUXI ME INSTALLATEUR SUPPORTE LE HAU...

Page 80: ...Enlevez toutes les vis qui tiennent les panneaux lat raux TAPE 3 R installez chacun des panneaux sur le c t oppos en faisant le processus inverse Fixer les supports de montage lectriques avec les atta...

Page 81: ...les supports de montage RA GAUCHE RA DROITE 4 6 INSTALLATION DU CONTR LE DE COMBUSTION RA GAUCHE Emplacement du contr le de combustion dans les configurations gauche et droite du RA IMPORTANT Cette t...

Page 82: ...l aide des attaches fournies ASSUREZ VOUS D ORIENTER CORRECTEMENT LE VOLET D AIR COMME ILLUSTR EN HAUT EN BAS Le bo tier de cont le de combustion est fix au panneau arri re l aide de 3 vis Une vis la...

Page 83: ...mbustion d tre vacu s de la chambre de combustion Pour combler les espaces cartez les d flecteurs en fibre pour qu ils soient bien appuy s de chaque c t comme illustr TAPE 5 Poursuivez l installation...

Page 84: ...E ET L ENCEINTE AVERTISSEMENT J J K K A A A A A A A A A A A A A A A A A A A A A A A B B C C C H D D E E F F G I I DOOR HANDLE DOOR SPRING WASHER SPACER DOOR HANDLE LATCH LOCK WASHER NUT NOTE Position...

Page 85: ...3 Fournaise hybride HMF150 combin e bois et lectrique voir la section 5 4 Fournaise hybride HMF150 combin e bois huile lectrique voir la section 5 5 5 0 CONFIGURATION DU RA GAUCHE ET DROIT AVEC D AUT...

Page 86: ...comburant aux deux fournaises Une ventilation insuffisante est dangereuse voir la section 3 2 air comburant ext rieur 7 Consultez les directives du fabricant 8 N utilisez pas de coudes dont le rayon...

Page 87: ...d appoint avant d en faire l entretien 16 Consultez les directives du fabricant de la fournaise originale relativement aux dimensions minimales des conduits les emplacements sur le caisson o il est p...

Page 88: ...ignez les trous de la partie inf rieure du support et les trous de guidage dans le haut de la fournaise Fixez l aide de vis t te hexagonale Fixez le rebord sup rieur du support de l interrupteur sur l...

Page 89: ...FFICACIT DE LA FOURNAISE ET ANNULERA LA GARANTIE Apr s avoir tabli les valeurs de r glages manipulez soigneusement les fils l int rieur de la bo te de jonction afin d viter que le couvercle de la bo t...

Page 90: ...min dans le syst me de conduits NOTE L ensemble comprend les directives et les sp cifications des l ments suivants a Moteur ECM de la fournaise originale le relais joue le r le d un contact sec pour...

Page 91: ...l aide des pieds d ajustement en alignant le trou de d gagement des brides de fixation avec les trous de guidage sur le panneau de la fournaise TAPE 7 Soulevez le module de soufflerie par le c t o se...

Page 92: ...tez la gaine des fils en la glissant suffisamment loin pour viter d endommager le c blage lors de l ajustement de la longueur du conduit flexible De l extr mit du conduit flexible mesurez une longueu...

Page 93: ...AISE HYBRIDE HMF150 UTILIS E COMME FOURNAISE AU BOIS AUTONOME RA GAUCHE RA DROITE TAPE 10 Retirez le contenu de l ensemble du module de la fournaise l huile HMFK OFRF40 ou HMFK OFAFG et assurez vous q...

Page 94: ...SEMBLAGE INAD QUAT DES COMPOSANTS DE LA FOURNAISE L HUILE PEUT NUIRE AU RENDEMENT ET ENDOMMAGER LES COMPOSANTS OU LA PROPRI T SENS DE CIRCULATION DE L AIR DEPUIS LE MODULE DE LA SOUFFLERIE CHANGEUR DE...

Page 95: ...RE JOINT D TANCH IT VOYANT EN VERRE JOINT D TANCH IT DE LA BRIDE BAS DE LA FOURNAISE CHAMBRE DE COMBUSTION DE LA FOURNAISE L HUILE DEVANT DE LA CHAMBRE DE COMBUSTION AVERTISSEMENT TOUS LES HARNAIS DE...

Page 96: ...ge Les fils l autre extr mit du harnais devraient passer dans le bo tier appropri situ sur le cadre du br leur huile Le conduit flexible devrait tre fix au bo tier l aide du raccord flexible 90 l aide...

Page 97: ...de l interrupteur comme indiqu la Figure A Fixez toutes les cosses drapeau aux bornes de l interrupteur puis installez le fil de mise la terre sur le cadre de l interrupteur D terminez les valeurs li...

Page 98: ...xagonale 9 vis NOTE En raison des tol rances de fabrication il est possible que les trous de d gagement de la plaque ne s alignent pas parfaitement avec les trous de guidage sur la face avant du panne...

Page 99: ...erceuses 1 4 t te hexagonale CONFIGURATION DU RA GAUCHE LE REBORD SUP RIEUR DU PROTECTEUR DE CHALEUR S APPUIE SUR LE BAS DE LA BUSE LA BASE HORIZONTALE DU PROTECTEUR DE CHALEUR EST LA PLUS PR S DE LA...

Page 100: ...deux conduits ils sont surtout utilis s lorsque la longueur des tuyaux est excessive ou que le d but des conduites d aspiration se trouve sous le niveau du br leur huile Pour obtenir des pr cisions su...

Page 101: ...ectrique et assurez vous que le contenu correspond celui de la liste des composants annex e au manuel qui accompagne le module de la fournaise lectrique TAPE 8 Disposez c te c te les modules de la sou...

Page 102: ...Le connecteur flexible de 90 doit aussi tre pass dans le trou et fix avec un crou l int rieur du module PANNEAU LAT RAL DE LA SOUFFLERIE HARNAIS DE LA SOUFFLERIE BO TIER LECTRIQUE INF RIEUR VERS LA SO...

Page 103: ...rouvent sur la plaque bornes dans le haut de la bo te de contr le principale Acheminez le fil de commande autour de la partie arri re de la fournaise HMF150 Passez le sous le module de la fournaise le...

Page 104: ...1 7 de la SECTION 5 4 FOURNAISE HYBRIDE HMF150 COMBIN E BOIS LECTRIQUE TAPES 8 19 Suivez les tapes 2 12 de la SECTION 5 3 FOURNAISE HYBRIDE HMF150 COMBIN E BOIS HUILE TAPE 21 Voir la SECTION 7 0 RACC...

Page 105: ...6 Raccord de 5 7 7 Coude de 5 90 8 Soupape barom trique 9 AVERTISSEMENT Afin de respecter les d gagements aux mat riaux combustibles le conduit d vacuation de la fournaise l huile doit tre install du...

Page 106: ...S AUX MAT RIAUX COMBUSTIBLES 48 18 24 1 25 D GAGEMENTS AUX MAT RIAUX COMBUSTIBLES D GAGEMENTS POUR ENTRETIEN CONFIGURATION DU RA DROITE VUE DE C T DU MODULE DE LA SOUFFLERIE Le dessin n est pas l chel...

Page 107: ...urnaise HMF150 une fournaise au gaz ou au propane existante vous devez avoir deux chemin es distinctes 6 4 CONFIGURATION DE L VACUATION DANS LE CAS D UNE FOURNAISE ANNEX E IL EST STRICTEMENT INTERDIT...

Page 108: ...APPOINT AU CONDUIT D ALIMENTATION EN AIR FROID DE LA FOURNAISE EXISTANTE NE PAS RESPECTER CETTE DIRECTIVE POURRAIT ENTRA NER DES DOMMAGES LA PROPRI T ET UN RISQUE D INCENDIE POUR OBTENIR PLUS D INFORM...

Page 109: ...courant contre co FOURNAISE AU BOIS ANNEX E FOURNAISE EXISTANTE HORIZONTALE H Si l appareil est install sur un plancher combustible il doit tre plac sur une base de protection La base de protection e...

Page 110: ...commande de la soufflerie du module de la fournaise lectrique K Rouge L Rouge 7 0 RACCORDEMENTS LECTRIQUES ET SCH MAS TOUT LE C BLAGE ET LES BRANCHEMENTS LECTRIQUES DOIVENT TRE EFFECTU S PAR UN LECTR...

Page 111: ...E HMF150 C BLAGE DE L APPAREIL D APPOINT 3 JUIN 2010 A 3 2 N 12 120 V 24 V R G B C INTERRUPTEUR BASCULE 1 2 3 4 5 6 7 8 9 10 11 12 TT D E F C1 C2 NOTES IMPORTANTES AU SUJET DE L INSTALLATION A D BRANC...

Page 112: ...7 8 11 12 14 15 16 MOTEUR DU VOLET D AIR INTERRUPTEUR BOIS 120 V 120 V 24 V 24 V PRODUITS NAPOL ON SCH MA DES CON TR LES ET DES CIRCUITS DE LA FOURNAISE HMF150 C BLAGE DE L APPAREIL AU BOIS SEULEMENT...

Page 113: ...BOIS 120 V 120 V 24 V 24 V PRODUITS NAPOL ON SCH MA DES CON TR LES ET DES CIRCUITS DE LA FOURNAISE HMF150 C BLAGE DE L APPAREIL COMBIN BOIS LECTRIQUE 3 JUIN 2010 A INTERRUPTEUR BASCULE 1 2 3 4 5 6 7 8...

Page 114: ...0 V 24 V 24 V PRODUITS NAPOL ON SCH MA DES CON TR LES ET DES CIRCUITS DE LA FOURNAISE HMF150 C BLAGE DE L APPAREIL COMBIN BOIS HUILE 3 JUIN 2010 INTERRUPTEUR BASCULE 1 2 3 4 5 6 7 8 9 10 11 12 E F SOU...

Page 115: ...V CA R G COM 120 V CA L1 N HUILE 1 2 3 4 9 10 13 5 6 7 8 11 12 14 15 16 MOTEUR DU VOLET D AIR THERMOSTAT BOIS 120 V 120 V 24 V 24 V PRODUITS NAPOL ON SCH MA DES CON TR LES ET DES CIRCUITS DE LA FOURN...

Page 116: ...r de contr le de l air de combustion se trouvent un levier et une poign e Pour augmenter la combustion poussez la poign e vers le bas jusqu l extr mit de la fente Faites pivoter l attache aussi situ e...

Page 117: ...SUREZ VOUS DE METTRE L INTERRUPTEUR D T LA POSITION OFF SI VOUS LE LAISSEZ LA POSITION ON LES PRODUITS D CHAPPEMENT SERONT TROP REFROIDIS MESURE QU ILS CIRCULERONT DANS LES TUYAUX DE L CHANGEUR DANS L...

Page 118: ...tion lente chargez des b ches plus grosses de fa on compacte Pour des dur es de combustion plus longues laissez un lit de braises d une paisseur de 1 2 pour une meilleure combustion secondaire creusez...

Page 119: ...isfaisante Une fois que les portes sont ferm es vous observerez peut tre un changement dans le comportement des flammes si la porte vitr e est install e Elles deviendront plus petites et plus paresseu...

Page 120: ...la porte lentement afin d viter les d versements de fum e Lorsque vous alimentez le feu utilisez une longue paire de gants protecteurs Gardez une petite pelle en acier proximit elle peut tre utilis e...

Page 121: ...RPORELLES UNE MISE AU REBUT INAD QUATE DES CENDRES CAUSE DES INCENDIES NE JETEZ PAS LES CENDRES DANS DES BO TES DE CARTON DANS LA COUR ARRI RE ET NE LES ENTREPOSEZ PAS DANS LE GARAGE SI VOUS UTILISEZ...

Page 122: ...extincteur ou un boyau d arrosage 4 Ne faites pas fonctionner l appareil avant d tre certain que la chemin e n a pas t endommag e 9 1 FEU DE CHEMIN E OU FEU HORS CONTR LE 9 0 ENTRETIEN Toutes les mai...

Page 123: ...ent environ 50 d humidit tandis qu une fois s ch il n en contient que 20 Quand le bois br le l eau bout en consommant une partie de l nergie qui aurait d produire de la chaleur Plus le bois est humide...

Page 124: ...nent la vitre Enlevez toute la vitre bris e 9 6 3 Enveloppez les rebords de la nouvelle vitre avec un joint de fibre de verre en forme de U et couvrez 1 4 de chaque c t 9 6 4 Mettez ensuite la vitre e...

Page 125: ...se condensent dans le conduit relativement froid de la chemin e d un appareil br lant lentement et lorsqu elle prend feu la cr osote produit un feu extr mement chaud Inspectez votre chemin e pour des...

Page 126: ...mps le joint peut devenir l che Vous devrez le remplacer 9 11 SOINS DE LA VITRE S IL Y A LIEU Si vous ne nettoyez pas les d p ts r guli rement la vitre risque de rester marqu e en permanence Normaleme...

Page 127: ...0017 VITRE DE PORTE C RAMIQUE INSERTION POUR PORTE PLEINE JOINT D TANCH IT DE PORTE JOINT D TANCH IT POUR VITRE DE PORTE W090 0015 BRIQUE R FRACTAIRE A W090 0179 BRIQUE R FRACTAIRE B W090 0181 BRIQUE...

Page 128: ...ou ajouter un chapeau tirage induit peut aider Voir la section S LECTION DU BOIS pour plus de d tails La hauteur de la chemin e et les conditions ext rieures peuvent nuire au tirage Dans ces cas il es...

Page 129: ...isibles ne seront pas la responsabilit de NAPOL ON Toutes les pi ces remplac es selon les termes de la Garantie Vie Limit e du Pr sident sont sujettes une limite d une seule r clamation Durant les dix...

Page 130: ...HISTORIQUE D ENTRETIEN Historique d entretien Wolf Steel Cet appareil doit tre entretenu annuellement selon son usage Nom du technicien D taillant Date Travail effectu Probl mes particuliers H Histori...

Page 131: ...W415 0910 A 09 16 10 65 14 0 NOTES...

Page 132: ...W415 0910 A 09 16 10 66 14 0 NOTES...

Reviews: