W415-0910 / A / 09.16.10
24
“B” HARNESS
CONNECTOR
CONTROL WIRE FOR
BLOWER CONTROL
ON ORIGINAL
FURNACE FIELD
INSTALLATION
RELAY BLOCK
SUPPLIED IN
“ADD ON ”
MODULE KIT
LINES 12 & N TO
ENGAGE COIL
ON RELAY
RG
LOWER ELECTRICAL BOX - MAIN HARNESS HMF150
NOTE
1. Adjusted motor speed when operating the original furnace, should balance air
fl
ow thru, so that
temperature and pressure differential measured between warm air supply plenum remain the same
before and after addition of the “Add On”.
2. Adjustment of motor speed when operating “Add On” should provide an air
fl
ow of 1100-1300 CFM
thru the ducting system.
NOTE
- Instructions and speci
fi
cations to be included in kit for:
a) ECM motor in original furnace
• relay acts as dry contact for G contact on G13 control board.
b) PSC motor in original furnace (TYPE 8A05A-101)
• spec White Rogers fan control centre supplied by installer
• control wire can be from R&G contacts of fan centre to dry contact on relay in lower control box
HMF150
c) PRECAUTION - New fan centre to have same power source as original furnace.
d) Motor speed may need to be increased to overcome increased static pressure:
• PSC - move to higher speed as needed
• ECM - adjust taps or control as needed
Summary of Contents for HYBRID 150
Page 6: ...W415 0910 A 09 16 10 6 AIR FLOW CIRCULATION AND HEAT TRANSFER COMBUSTION AIR FLOW...
Page 64: ...W415 0910 A 09 16 10 64 13 0 SERVICE HISTORY...
Page 65: ...W415 0910 A 09 16 10 65 14 0 NOTES...
Page 66: ...W415 0910 A 09 16 10 66 14 0 NOTES...
Page 72: ...W415 0910 A 09 16 10 6 CIRCULATION D AIR ET CHANGE DE CHALEUR CIRCULATION DE L AIR COMBURANT...
Page 131: ...W415 0910 A 09 16 10 65 14 0 NOTES...
Page 132: ...W415 0910 A 09 16 10 66 14 0 NOTES...