412 – HI U-PDU
ZKP-Number: 2.0141.931
Limit value 1
Cause
Corrective action
Injector voltage too high
1. Check cabling.
2. Check supply.
3. Contact Service.
413 – HIHI U-PDU
ZKP-Number: 2.0141.932
Limit value 2
Cause
Corrective action
Injector voltage too high
1. Check cabling.
2. Check supply.
3. Contact Service.
414 – HI Level Water Fuel Prefilter
ZKP-Number: 2.0156.931
Limit value 1
Cause
Corrective action
Water level in fuel prefilter too
high
u
Drain water (→ Page 221), (→ Page 223).
415 – LO P-Coolant Intercooler
ZKP-Number: 2.0107.921
Limit value 1
Cause
Corrective action
Coolant pressure in intercooler
too low
u
Top up coolant (→ Page 279).
416 – SS P-Coolant Intercooler
ZKP-Number: 2.0107.922
Limit value 2
Cause
Corrective action
Coolant pressure in intercooler
too low. Engine stop.
u
Top up coolant (→ Page 279).
172 | Troubleshooting | MS150093/05E 2018-12
TIM-ID: 0000008506 - 006