390 – AL MCR exceeded
ZKP-Number: 1.1085.009
Cause
Corrective action
DBR/MCR feature: MCR
exceeded.
1. No action required if alarm only applied temporarily.
2. Contact Service if alarm applied constantly.
392 – HI T-Coolant Red
ZKP-Number: 2.0129.931
Limit value 1
Cause
Corrective action
Redundant coolant temperature
reading too high
1. Check cabling.
2. Contact Service.
393 – SS T-Coolant Red
ZKP-Number: 2.0129.932
Limit value 2
Cause
Corrective action
Redundant coolant temperature
reading too high. Engine stop.
1. Check wiring and sensor.
2. Contact Service.
394 – LO P-Lube Oil Red
ZKP-Number: 2.0112.921
Limit value 1
Cause
Corrective action
Redundant lube oil pressure
reading too low
1. Check wiring and sensor.
2. Contact Service.
395 – SS P-Lube Oil Red
ZKP-Number: 2.0112.922
Limit value 2
Cause
Corrective action
Redundant lube oil pressure
reading too low
1. Check wiring and sensor.
2. Contact Service.
396 – TD T-Coolant Sensor Deviation
ZKP-Number: 1.0480.193
Cause
Corrective action
Maximum coolant temperature
deviation
1. Check wiring and sensor.
2. Contact Service.