SUPREMATouch
44
Operation of the System
MSA
US
Sensors Submenu
Through the submenu "Sensors", the parameters of the predefined remote sensing heads can be
viewed as well as set for some predefined parameter in specific ranges. The menu contains the
following items described consecutively in this section:
-
Head parameters
-
Status texts
-
Gas name
-
Measuring range
-
Dimensions
-
Lin.- tables
-
Assignment
-
Allocation
Head parameters
Fig. 20
“Head parameter”
This window displays the significant parameters of the remote sensing heads. During normal op-
eration the SUPREMATouch software permanently checks the detector output signal sent by to
the SUPREMATouch. In case the detector output signal falls below UA
min
an inhibit indication,
and below UA
idle
a fault indication will be set for this measuring point. In case the detector output
signal exceeds UAover an overflow will be indicated. Data fields that are not used for a specific
remote sensing head are empty.
It is possible to enter user specific data for some active [4…20 mA signal] remote sensing heads.
For this purpose, the following fields can be changed: Name [English and local language], UA
min
,
UA
idle
, UA
over
and T
supp
. The “ID” of modifiable remote sensing heads begins with the value
“10000” and their status is displayed as “changeable”.
The functions of the individual window elements are described below:
ID [Remote sensing head ID]
Field type: Selection
A remote sensing head can be selected in this field by means of its ID
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...