Fig. 106 SUPREMA CAN-Bridge CBM
The SUPREMA CAN BRIDGE is supplied with 24V DC (X101). The CAN Bus of the Basic Rack
is connected to NET 0 (X400), and the satellite rack is connected to NET1 (X400) (Exact connec-
tion assignments are to be seen from the CAN Bridge hardware manual).
For parameter setting, a serial interface (DSUB plug connector X100) is provided. The CAN
Bridge parameters can be set using a terminal program (e.g. Hyper Terminal for Windows).Details
of this process are described below.
The code switches SW211 and SW210 of the CAN Bridge are only for internal service purposes
and must always be in position 0. When both LED‘s (1 and 2) are on the status is ‘good‘. If there
is a failure at one of the two CAN buses, the corresponding LED will flash, LED 1 for NET 1, and
LED 2 for NET 0.
For the correct function of the SUPREMA CAN bridge, some points must be considered:
NOTE: 32 filters max. may be set, i.e., in a satellite, 9 MGO/MAO modules max. can be integrated.
The number of MDA/MAI modules per rack is not limited.
As to a):
Fig. 107 Baudrate at the Central Rack
a)
Baudrate setting at the Central Rack (depends on the number of measuring points)
b)
Baudrate setting at the satellite rack (depends on the distance of the satellite)
c)
Rack number (Dip switch at the MIB module)
d)
Components of the Satellite racks (Plug positions of the MDA, MGO, MAO, MAI modules)
Measuring points
Bit rate setting in kB/s
Bridge
Simplex/Duplex
Command
1 - 256
250
B0:4
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...