SUPREMATouch
88
Maintenance and Service
MSA
US
6.3
Replacement of Sensors
Sensors which are no longer able to reach the minimum signals, the zero point of which can no
longer be adjusted, or which no longer function properly for some other reason must be replaced.
For this purpose, inhibit the corresponding measure point in the “Setup/Measure Points” menu.
Then perform the following steps:
-
Remove the connector plug of the sensor from the MAT/MAT TS module or the sensor cable
from the MGT 40 TS module.
-
Pull out the old sensor, put the new [properly functioning] sensor in its place, and install it.
-
Reconnect the connector plug of the sensor to the MAT/MAT TS module or the sensor cable
to the MGT 40 TS module.
-
Perform a first calibration as described in Chapter 6.1 , under consideration of the required
sensor recovery time.
-
Check the configuration of the sensors in the “Setup/Measure Points” menu.
-
Unlock the measure point.
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...