Technical data:
LWL Line Specification:
* Other line lengths after consultation with MSA AUER.
For use with the SUPREMATouch, multi mode firbes are required. For further technical data and
operating conditions, see the LWL Converter Manual.
10.6 Connection of the Sensors
General Instructions
-
Incorrect connection of the sensors can cause damage both to the SUPREMA and to the sen-
sor itself.
-
It must be ensured that the adapter modules corresponding to the sensors are plugged into the
appropriate MAI module (verify that the sequence is correct (Chapter 10.3).
-
After the sensors have been connected, they are to be separated electrically again by pulling
the connector plug on the MAT or MAT TS module. They are to be plugged in again individually
only as part of the startup procedure (Chapter 11). If the MGT 40 TS module is being used, this
is to be disconnected by pulling the ribbon cable connector to the MUT module.
-
To ensure that the system will function correctly, the EMC Directives and the measures derived
from them must be observed Chapter 10.1).
The cables are to be connected to the SUPREMA and to the sensors in observance of the allow-
able cable cross sections and the maximum cable lengths. A detailed description of the connec-
Voltage supply
10 V ... 48 VDC
Current compumption
max. 100 mA
Connection of bus interface
CANopen, 4-pin COMBICON
Bus terminator
120 Ohm connectable
Data rate
10, 20, 50, 125, 250, 500, 800 kBit/s adjustable
Connection LWL interface
ST (B-FOC)
Wave length
850 nm
Operating temperature
-20 °C to +60 °C
Function text EX AM
+5 °C to +55 °C
Storage temperature
-40 °C to +85 °C
Dimensions (W x H x D)
22.5 mm x 105 mm x 115 mm
Weight
approx.120 g
Humidity
10 % ... 95 %, non-condensing
Line type
Wave length
Connector
Damping
Maximum length
F-S200/230
850 nm
ST
®
(B-FOC)
8 dB/Km
1500
F-G 62.5/125
850 nm
ST
®
(B-FOC)
3 dB/Km
2000*
F-G 50/125
850 nm
ST
®
(B-FOC)
2.5 dB/Km
2000*
WARNING
Always turn off the voltage to the system before connecting the sensors.
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...