Connection of Peripherals
MSA
US
reset manually (status no longer exists). The current status of the sampling point with the data
structure shown in Figure 166: Protocol printer, Data Structure is printed out along with the date
and time of the most recent change of status.
NOTE: This formatting can be changed by the user!
12.3 Bus Connection
To connect the SUPREMA system to existing industrial control systems, it is necessary to com-
municate with other data buses for processing of measuring values, alarms/failures.
The signal conversion necessary is realised by SUPREMA gateways.
NOTE: 2 gateways per CAN channel can be connected.
NOTE: The gateways are not included in the approval!
For the time being, the following bus systems are supported:
-
Modbus RTU Standard
-
Modbus TCP, Description of function - see Software Manual "SUPREMA Gateway CAN/
Modbus TCP with SUPREMA-CANopen Firmware"
-
Profibus DP
ATTENTION: Modbus can only be used for data collection or record keeping with regards to com-
bustible gas detection and not for performance verification.
Further data bus systems on request.
SUPREMA Gateway CAN/Modbus RTU (PKV30)
(Not contained in EC-type examination certificate DMT 03 ATEX G 003 X)
Fig. 167 Connection the SUPREMA to external systems using a Modbus RTU gateway
The gateway is installed on a mounting rail in the cabinet and requires a 24 V dc supply voltage
(X1). The SUPREMA transfers the data via the CAN bus which is connected to X2 at the gateway.
For data supply to the Modbus, there are 3 physically different serial interfaces (X3) and 3 different
data formats to be selected.
The gateway generally operates as a slave for the CAN bus and Modbus. The SUPREMA and the
control system must therefore initiate the gateway to send data.
Enclosed with the gateway are the following 5 manuals for installation, parameters and operation:
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...