MSA AUER
MSA
Operation of the System
SUPREMATouch
65
US
Calibration history
This history saves the calibration process data for each input. Up to four entries can be stored for
each input, and older entries are overwritten, except for the first calibration and pre-settings.
Fig. 37
Calibration history
When an input is selected, the appropriate calibration history is displayed in the corresponding
field, if the input has already been calibrated. The entry for each calibration process consists of
two rows, first the test gas and then the zero gas setting. A pre-setting entry is made up of only
one row.
If a separate zero adjustment has been carried out, the values for “Concentration” and “Measure-
ment value” are blanked in the Span Gas Measurement line by “———”.
The type of entry is identified by a character in the first column:
I
Bridge current setting [IBR]
Z
Presetting Zero point [ZERO]
S
Presetting Sensitivity [SPAN]
*
First calibration
Number n
n-last calibration
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...