SUPREMA
234
Redundant Systems
MSA
US
13.2 Function of Redundant Systems
The circuit diagram of the redundant system shows its design and function: The signal from the
sensors connected to the MAT modules is amplified by the sensor modules (MCI, MPI) to give a
voltage of approx. 400 ... 2000 mV. By 2 separate A/D converters (on MAI + MAR), the measuring
signal is digitised and transferred to the two processing channels A and B by passing it through
the MDA modules (A + B) to the separate CAN Bus systems (channels). The signal processing
and evaluation of one channel is carried out independently from the other. The Table “Modules
of the Rack” shows the different components of the rack for a non-redundant and a redundant sys-
tem.
Module Functions
MDA Module
= Measuring Signal Input
MCP Module
= Measuring Signal Evaluation
MGO Module
= Alarm Output
MAI Module
= Analog Input (ADW 1)
MRA Module
= Analog Redundant (ADW 2)
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...