SUPREMATouch
138
Installation
MSA
US
Rack-CAN Node Number (BGT No.)
In the following, the CAN node numbers to be set when several racks [BGTs] are being used are
listed. The standard setting for an individual rack is BGT 1.
Fig. 66
Rack -CAN Node Number
Explanation of the symbols
CAN-BUS Terminating Resistors
Both CAN bus systems (CAN-A + CAN-B) of the SUPREMA must have a terminating resistor at
each end of the bus. One end of the bus is located on the MDO module. A terminating resistor is
permanently connected here. For a 1-rack system, the other end of the bus is at the rear-panel
wiring of the MIB. If the system consists of only one rack, switches 1 and 2 of the DIL switch must
be set to the lower position.
If an additional rack is provided for the system, the racks are connected to each other at the rear
via the MST modules with ready-made CAN bus cables.
For a “multi-rack” system, the DIL switch contacts 1 and 2 (CAN-A, CAN-B) of the last rack – by
which the CAN BUS is ending - must be set to the lower position, all DIL switch contacts 1 and 2
(CAN-A, CAN-B) on the intermediate racks must be set to the upper position.
CAN
FREE
Baud
Rack
A
B
A
B
4
2
1
4
2
1
1
2
3
4
5
6
7
8
9
10
In the case of alternative assembly
10
9
8
7
6
5
4
3
2
1
BGT 1
Standard setting for a single rack (BGT)
ON
ON
ON
BGT 2
ON
ON
OFF
BGT 3
ON
OFF
ON
BGT 4
ON
OFF
OFF
BGT 5
OFF
ON
ON
BGT 6
OFF
ON
OFF
BGT 7
OFF
OFF
ON
BGT 8
OFF
OFF
OFF
= Any switch
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...