13.3 Design of the Redundant System
Components of the Rack
In the non-redundant version, the system is consists of only one channel (channel A). By retrofit-
ting modules for channel B, the system can be designed to be redundant in one rack for up to
64 measuring points.
NOTE: Retrofitting necessary modules for redundant design must only be carried out voltage-free,
i.e. the whole SUPREMA system must be switched off. The following new startup must be carried
out with consideration of the necessary configuration and parameter setting steps.
NOTE: When retrofitting, the Regulations for Handling Electrostatic Sensitive Components must
be followed!
Fig. 174 Modules of Rack
By adding further racks (8 max. per system) and the appropriate modules, the system can be ex-
tended up to 256 measuring points with up to 512 outputs.
-
The MAR modules are plugged into the MAI modules.
-
The MGO modules: configuration is by plug-in jumpers for CAN A or CAN B
-
The same number of MGO modules at CAN A and CAN B
-
Connection of 2 gateways at CAN A and CAN B (Modbus, Profibus)
Slot
Name
Non redundant (Channel A)
Redundant (Channel B)
1
Slot 1
MCP
MCP
2
Slot 2
MCP
3
Slot 3
MDC + MDO
MDC + MDO
4
Slot 4 / MDA 1
MDA
MDA
5
Slot 5 / MDA 2
MDA
6
Slot 6/POS 1
MAI + MAR
7
Slot 7/POS 2
MAI
MAI + MAR
8
Slot 8/POS 3
MAI
MAI + MAR
9
Slot 9/POS 4
MAI
MAI + MAR
10
Slot 10/POS 5
MAI
MAI + MAR
11
Slot 11/POS 6
MAI
MAI + MAR
12
Slot 12/POS 7
MAI
MAI + MAR
13
Slot 13/POS 8
MAI
MAI + MAR
14
Slot 14/POS 9
MGO
MGO
15
Slot 15/POS 10
MGO
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...