MSA AUER
MSA
Operation of the System
SUPREMATouch
31
US
DO [Inhibit Digital Outputs]
Field type: Check box
If this checkbox is enabled, assigned
outputs will not be activated
in the event of an alarm or
failure of selected measuring points! During a multiple assignment [Voting], the corresponding
measuring point is ignored when assessing the status . If this check box is enabled, for at least
one of the measuring points, the inhibit LED on the MDO as well as the common alarm relay 'In-
hibit' starts blinking with a frequency of 1 Hz.
Information, Sensor Data and Alarms
Field type: Button
Pressing the appropriate button will display the corresponding subwindow.
OK
Field type: Button
Press this button to accept the settings entered in all three subwindows for the selected input. Af-
ter the button is pressed, the parameters are immediately checked to see whether they are valid.
If the parameters are valid, they become part of the system’s parameter set. If they are not valid,
a warning appears.
Cancel
Field type: Button
Press this button to discard the settings entered in all three subwindows for the selected input.
Clear
Field type: Button
Press this button to delete all parameters for the selected input. The input will then return to the
status it had before being set up the first time. Default values are used as the preliminary settings
for the input of certain fields. The delete function will not work if the input is being calibrated or
linked with a relay output.
“Information” subwindow
The “Information” subwindow contains general data on the selected input.
Tag
Field type: text
Enter a customer specific designation for the selected input
Marking
Field type: text
Enter a customer specific description for the selected input
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...