6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
44
6796573/02 EN
MSENSE
®
VAM
6.1.1.1 Minimum distances
NOTICE
Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due
to overheating.
► Keep the ventilation slots clear.
► Ensure sufficient distance to neighboring components.
► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
Reliable operation of the device in the permitted temperature range requires
that you maintain the following minimum distances to the control cabinet and
to neighboring components:
Minimum distance
To the floor of the control cabinet
88.9 mm (3.5 in)
Corresponds to 2 RU
To the roof of the control cabinet
Between assemblies on the bus bar and assem-
blies on the remote cap rail
Table 11: Minimum distances in the control cabinet
Figure 22: Example depiction of the minimum distances in a control cabinet
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.1.1.2 Fastening the cap rail
The cap rail is required to mount a bus bar or a device's remote assemblies
in a control cabinet. Only use the following types of cap rails in accordance
with EN 60715:
▪ TH 35-7.5
▪ TH 35-15
The cap rail may not be painted or lacquered.