8 Operation
Maschinenfabrik Reinhausen GmbH 2021
104
6796573/02 EN
MSENSE
®
VAM
Parameter
Description
Activate remote mode
If the assigned event is active, the device
activates remote mode.
Activate local mode
If the assigned event is active, the device
activates local mode.
Table 20: Functions available
In order to establish the link, you have to enter the corresponding event
number in the desired parameter.
Note that you can only enter the event numbers of the
Generic digital input
or
Generic SCADA command
events.
If you enter event number 500, the link is disabled.
To link the function, proceed as follows:
ü
The desired event number is known.
1. Go to
Settings > Parameters > Link functions
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
8.7.8 Temperature monitoring
You can set four limit values for monitoring the temperature. If the measured
temperature is greater than limit value > or >>, the device triggers an event
message. If the measured temperature is less than limit value < or <<, the
device triggers an event message.
You can view the temperature curve under "Information".
Figure 80: Temperature monitoring