8 Operation
Maschinenfabrik Reinhausen GmbH 2021
129
6796573/02 EN
MSENSE
®
VAM
Ensure that the configuration of the digital inputs and outputs is suitable for
the functions used. Otherwise, malfunctions may occur in the device and
the connected periphery.
The following information is displayed in tabular form for configuring the digi-
tal inputs and outputs. Grayed out elements cannot be changed.
Property
Options
Function
Function of the digital input (I: ...) or the digital output (O: ...). You
can adjust the designation.
Signal type
Select signal type: Digital input
Configuration
DI: High active or low active
DO: N/O contact (NO), N/C contact (NC); Note: If the device is dis-
connected or in the event of an error, the digital outputs are always
open (no bi-stable relay).
Assembly/
channel
Channel of the DIO assembly to which the function is linked. Func-
tions that are not linked with a channel are identified with "-". Note
the connection diagram supplied.
Table 35: Configuration of the digital inputs and outputs
Figure 93: Configuring digital inputs and outputs
The operation described below is only possible if you access the visualiza-
tion using a computer. You can only change the configuration of the digital
inputs and outputs if you have a Parameter Configurator or Administrator
role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin