Configuring AIO
To configure the device's analog inputs and outputs, proceed as follows:
1. Go to
Settings > AIO configuration
.
2. Configure the properties as desired.
3. Press the
Accept
button.
4. Confirm the security prompt with
Save
to save the changes.
8.11 Tap position table
You can enter individual names for the tap positions in this menu.
8.12 Menu Settings > Reset VAM
The software in the MSENSE® VAM monitoring system uses a self-learning
algorithm which approximates the limit values towards the vibro-acoustic sig-
nal progression as the number of tap-change operations increases. The sta-
tistics stored for this can be reset in this display window.
Resetting the counter
The first and the second anomalies in an evaluation cluster are indicated via
a yellow status message in the VAM analysis (Information menu). A third
anomaly arising in an evaluation cluster triggers an additional event mes-
sage. This event message is transmitted to a connected SCADA system.
By selecting "Counters", you reset the counters that are used to trigger the
events for the vibro-acoustic evaluation. The self-learned statistics are re-
tained.
Resetting the statistics
The stored statistics are used among other things to display the self-learned
limit value (yellow curve [
When you select "Statistics", you reset the self-learned statistics and the
counters that are used to evaluate the vibro-acoustic signals.