8 Operation
Maschinenfabrik Reinhausen GmbH 2021
138
6796573/02 EN
MSENSE
®
VAM
Function
If Input has a rising edge, the internal timer is set to
zero and starts to run.
When the internal timer has reached or exceeded the
parameter value, Output becomes TRUE and the
counter stops running.
If Input becomes FALSE, Output also instantly be-
comes FALSE.
If the value of Time_ms is less than the cycle time, the
cycle time applies instead.
Initial state
All inputs and outputs are FALSE.
Table 44: Switch-on delay function module
8.15.1.3.9 Switch-off delay
Description
TOFF, switch-off delay
Inputs
Trigger (BOOL)
Reset (BOOL)
Outputs
Output (BOOL)
Parameter
Time ms (UINT32), 1...1,000,000, default = 1,000
Function
If Input becomes TRUE, Output also instantly becomes
TRUE, this condition takes priority.
If Input has a falling input, the internal timer is set to
zero and starts to run.
When the internal timer has reached or exceeded the
parameter value, Output becomes FALSE and the
counter stops running.
If Input is FALSE and the Reset input becomes TRUE,
Output instantly and forcibly becomes FALSE and the
internal timer is set to the configured desired value.
If the value of Time_ms is less than the cycle time, the
cycle time applies instead.
Initial state
All inputs and outputs are FALSE.
Table 45: Switch-off delay function module
8.15.1.3.10 Pulse
Description
PLSE, pulse
Inputs
Trigger (BOOL)
Outputs
Output (BOOL)
Parameter
Time ms (UINT32), 1...1,000,000, default = 1,000