6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
64
6796573/02 EN
MSENSE
®
VAM
For the control cabinet connection, proceed as follows:
1. Connect the sensor cable shield to the grounding bar in the control cabi-
net using a shielded clamp. When doing so, only expose the cable shield
as much as is necessary for the shielded clamp.
Figure 44: Sensor cable shield connection
Tighten the cable screw connections on the control cabinet with the follow-
ing tightening torques: M20: 8 Nm, M32: 20 Nm.
2. Connect the sensor cable in accordance with the connection diagram pro-
vided (blue = signal, brown = signal ground, black = ground in control cab-
inet).
6.3.7 Connecting the motor-drive unit controller to the monitoring
system
To synchronize the vibro-acoustic signals with the tap position change, it is
necessary to measure the diverter switch operation in the motor-drive con-
troller. With the integration solution in the motor-drive unit, this connection is
already made at the factory.
With the "standalone" and "integration solution in the customer control cabi-
net" versions, you must make this connection yourself. To do so, connect the
position transmitter module of the motor-drive unit to the DIO assembly of
the vibro-acoustic monitoring system in accordance with the connection dia-
gram provided.
6.3.8 Connecting the temperature sensor
Depending on the application, one or more temperature sensors are in-
cluded in the scope of delivery. When making the connection, follow the con-
nection diagram on the associated dimensional drawing. Make the connec-
tion to the control cabinet in accordance with the connection diagram pro-
vided for the monitoring system.