6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
66
6796573/02 EN
MSENSE
®
VAM
Suitable equipment includes isolating devices in accordance with IEC
60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the
relevant circuits (voltage, maximum currents) when selecting the circuit
breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and circuits to be iso-
lated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor
You must connect the power supply circuit with a conductor cross-section of
at least 2.5 mm
2
(AWG 13) and protect it with a C6A or B6A type miniature
circuit breaker.
To connect the voltage supply, proceed as follows:
► Connect the power supply of the control cabinet to terminal X1 in accor-
dance with the connection diagram provided.
6.4 Checking functional reliability
To ensure that the device is wired correctly, check its functionality.
NOTICE
Damage to device and system periphery!
An incorrectly connected device can lead to damage to the device and sys-
tem periphery.
► Check the entire configuration before commissioning.
To check the functionality, proceed as follows:
► Apply voltage to the control cabinet.
ð
The device's control system boots up; after a brief period, the relay
switches the operating contact
STATUS OK
(DIO 28-15:1B).
The device is fully mounted and can be configured. The actions required for
this are described in the following chapter.