6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
63
6796573/02 EN
MSENSE
®
VAM
5. Shorten the sensor cable to the desired length. Loops or coil windings of
an excessive length are not permitted when routing the cable.
Figure 43: Sensor cable routing
1 Temperature sensor cable
2 Control cabinet
3 Vibration sensor cable
4 Transformer
5 On-load tap-changer head cover
If the control cabinet is farther away, extend the sensor cable with a
shielded cable in the motor drive cabinet or in a metal intermediate terminal
box.
Follow the information in the Cable recommendation [
51] section and implement continuous shielding.