8 Operation
Maschinenfabrik Reinhausen GmbH 2021
146
6796573/02 EN
MSENSE
®
VAM
Function
Output is calculated using the following formula:
Output = Min Out + (Max Out - Min Out) x
(Input – Min In) / (Max In – Min In)
Output is set to 0 and Error = TRUE when:
▪ Input is not within the parameters Min In and Max In
▪ Min In is greater than Max In
▪ Min Out is greater than Max Out
▪ Max In is the same size as Min In (division by zero)
Initial state
All inputs and outputs are FALSE.
Table 57: Scaling function module
8.15.1.3.22 Bridge
Designation
BRDG, Bridge
Inputs
Analog Input (REAL32)
Digital Input (BOOL)
Outputs
Analog Output (REAL32)
Digital Output (BOOL)
Parameter
-
Function
Copies the value of Analog Input to Analog Output and
Digital Input to Digital Output.
Initial state
All inputs and outputs are zero or FALSE.
Table 58: Bridge function module
8.15.1.3.23 RTOI
Description
RTOI, Real-to-Integer conversion
Inputs
Analog Input (REAL32)
Outputs
Analog Output (SINT32)
Parameter
-
Function
Copies the value of Analog Input to Analog Output and
converts REAL32 to SINT32.
Initial state
All inputs and outputs are zero.
Table 59: RTOI function module
8.15.1.3.24 ITOR
Description
ITOR, Integer-to-real conversion
Inputs
UINT32 (UINT32)
SINT32 (SINT32)
Outputs
Output U (REAL32)
Output S (REAL32)