6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
61
6796573/02 EN
MSENSE
®
VAM
6.3.6 Connecting the vibration sensor to the control cabinet
Depending on the application, one or more vibration sensors are included in
the scope of delivery. Repeat the following steps for a multi-column applica-
tion.
You must connect the vibration sensor to the control cabinet using the sen-
sor cable provided. Note the following information when routing the sensor
cable:
▪ Route the sensor cable with as much shielding as possible on the trans-
former (e.g. in the tube or cable duct) and along a conductive grounded
surface that runs without interruption.
▪ Route sensor cables separately from supply lines and do not create any
unnecessary loops.
▪ The vibration sensor cable can also be routed together with the tempera-
ture sensor cable in a protective tube.
▪ On the control cabinet, it is advantageous to have routing parallel to the
earthing cable that connects the transformer and the control cabinet to-
gether.
To route the sensor cable, proceed as follows:
1. Remove the vibration sensor cover cap.
Figure 41: Vibration sensor cover cap
2. Ensure that the sensor cable plug and the socket on the sensor are dry
and free of dirt. If this is not the case, clean and dry them with a cloth.