NICE7000 User Manual 5 System Commissioning and Functions
- 79 -
1. Check the field mechanical and electric wiring.
Before power-on, check the peripheral wiring to ensure component and personal safety.
The items to be checked include:
1)
Whether the component models are matched
2)
Whether the safety circuit is conducted and reliable
3)
Whether the door lock circuit is conducted and reliable
4)
Whether the shaft is unobstructed, and the car has no passenger and meets the
conditions for safe running
5)
Whether the cabinet and traction motor are well grounded
6)
Whether the peripheral circuit is correctly wired according to the drawings of the vendor
7)
Whether all switches act reliably
8)
Whether there is short-circuit to ground by checking the inter-phase resistance of the
main circuit
9)
Whether the elevator is set to the inspection state
10) Whether the mechanical installation is complete (otherwise, it will result in equipment
damage and personal injury)
2. Check the encoder.
The pulse signal from the encoder is critical to accurate control of the system. Before
commissioning, check the following items carefully:
1)
The encoder is installed reliably with correct wiring. For details on the encoder wiring,
see section 3.6.
2)
The signal cable and strong-current circuit of the encoder are laid in different ducts to
prevent interference.
3)
The encoder cable is preferably directly connected to the control cabinet. If the cable
is not long enough and an extension cable is required, the extension cable must be
a shielding cable and preferably welded to the original encoder cable by using the
soldering iron.
4)
The shielding cable of the encoder cable is grounded on the end connected to the
controller (only one end is grounded to prevent interference).
3. Check the power supply before power-on.
1)
The inter-phase voltage of the user power supply is within (380 V
±
15%), and the
unbalance degree does not exceed 3%.
2)
The power input voltage between terminals 24V and COM on the MCB is within (24
VDC
±
15%).
3)
The total lead-in wire gauge and total switch capacity meet the requirements.
Summary of Contents for NICE7000
Page 1: ......
Page 15: ......
Page 16: ...1 Safety Information and Precautions ...
Page 23: ...1 Safety Information and Precautions NICE7000 User Manual 22 ...
Page 24: ...2 Product Information ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 71: ...4 Use of the Commissioning Tools ...
Page 79: ...5 System Commissioning and Functions ...
Page 102: ...5 System Commissioning and Functions NICE7000 User Manual 100 ...
Page 103: ...6 Function Code Table ...
Page 134: ...6 Function Code Table NICE7000 User Manual 132 ...
Page 135: ...7 Description of Function Codes ...
Page 205: ...8 Troubleshooting ...
Page 224: ...8 Troubleshooting NICE7000 User Manual 222 ...
Page 225: ...9 EMC ...
Page 234: ...9 EMC NICE7000 User Manual 232 ...
Page 237: ......