7 Description of Function Codes NICE7000 User Manual
- 164 -
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-25
Attendant/Automatic
switchover time
0–200
0
s
★
It is used to set the switchover time from the attendant state to the automatic state. When
the value of this parameter is smaller than 5, this function is disabled,
If there is a hall call at current floor in attendant state, the system automatically switches
over to the automatic (normal) state after the time set in this parameter. After this running is
completed, the system automatically restores to the attendant state (F6-24 Bit2 must be set
to 1).
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-26
Emergency evacuation time limit
30–600
45
s
★
It sets the allowed emergency evacuation time.
If the time exceeds this value, the controller reports Err31.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-27
Emergency evacuation
function selection
0–65535
3
-
★
It is used to select the emergency evacuation-related functions. Each bit of the function code
defines a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
The functions defined by the binary bits are described in the following table.
Bit
Function
Description
Default
Bit0
Door 1 valid
In emergency evacuation state, the elevator under
opposite door control opens the corresponding door.
1
Bit1
Door 2 valid
1
Bit2
Emergency
evacuation time
protection
When the emergency evacuation time exceeds F6-26, the
controller reports fault Err31, and switchover from shorting
stator braking mode to controller drive based on time limit
cannot be performed.
0
Bit3
Manual control
The system automatically switches over to EPS and enters
the inspection state. You need to press the inspection up
and down buttons at the same time to perform emergency
evacuation running.
0
Bit4
Buzzer tweeting
The buzzer tweets at intervals in the emergency
evacuation state.
0
Bit5
HCB output
The HCB-B needs to installed additionally.
Set the terminal with the emergency evacuation function,
and the terminal will output the corresponding signal in the
emergency evacuation state.
0
Summary of Contents for NICE7000
Page 1: ......
Page 15: ......
Page 16: ...1 Safety Information and Precautions ...
Page 23: ...1 Safety Information and Precautions NICE7000 User Manual 22 ...
Page 24: ...2 Product Information ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 71: ...4 Use of the Commissioning Tools ...
Page 79: ...5 System Commissioning and Functions ...
Page 102: ...5 System Commissioning and Functions NICE7000 User Manual 100 ...
Page 103: ...6 Function Code Table ...
Page 134: ...6 Function Code Table NICE7000 User Manual 132 ...
Page 135: ...7 Description of Function Codes ...
Page 205: ...8 Troubleshooting ...
Page 224: ...8 Troubleshooting NICE7000 User Manual 222 ...
Page 225: ...9 EMC ...
Page 234: ...9 EMC NICE7000 User Manual 232 ...
Page 237: ......